Specifications

17
3.3.4.2 Relay Mode
Figure 3-31 Relay Mode
This display example shows that relay 1 is configured to operate in the Normally Off mode. The relay modes are:
1 ALARM
2 Normally Off (default)
3 Normally On
Relaymode1isaspecialcase.Thismodeisonlyavailableonrelay1anddedicatestherelaytofunctionasanalarmsignaltoasubsequentalarmormonitoringpanel.Thismodeforces
the relay to Normally Off mode with no turn on delay or minimum on time. See Section 3.1.4 for more detail regarding alarms
Fail Safe operation can be implemented by configuring a relay to operate Normally On, and wiring the circuit using the NC (normally closed) contact. In this way, if the control panel looses
power the relay will turn on the controlled device if it still has power.
3.3.4.3 Relay Turn On Delay
Figure 3-32 Turn On Delay
The default turn on delay is one minute and the maximum allowed value is fifteen minutes. The value is entered in two groups, 2 digits for the minutes and then 2 digits for the seconds. A
leading zero must be entered for each group if applicable.
3.3.4.4 Relay Minimum On Time
Figure 3-33 Minimum on Time
The default minimum on time is one minute and the maximum allowed value is fifteen minutes.
3.3.5 Configure Horn Submenu
Thecongurationparametersforthehornarethesameasthoseforrelays.Ahornwouldnotnormallyrequireaminimumontimebutthisparameterallowsamoreversatileconguration.
3.3.5.1 Horn Summary
Figure 3-34 Horn Summary
This display example shows that the horn has been configured to operate Normally Off, with a turn on delay and no minimum on time.
Notice that the horn number, 4, is underlined. This indicates that the digit keys can be used to jump to a particular relay, horn or strobe. The relays are numbers 1, 2 and 3; the horn is
number 4 and the strobe is 5.
3.3.5.2 Horn Mode
Figure 3-35 Horn Mode
This display example shows that the horn is configured to operate in the Normally Off mode. The valid modes are:
2 Normally Off (default)
3 Normally On
3.3.5.3 Horn Turn On Delay
Figure 3-36 Horn Turn On Delay
The default turn on delay is one minute and the maximum allowed value is fifteen minutes.
3.3.5.4 Horn Minimum On Time
Figure 3-37 Horn Minimum on Time
The default minimum on time is zero and the maximum allowed value is fifteen minutes.