Specifications
21
3.3.8.2 Alarm Buzzer Signal
Figure 3-54 Buzzer Alarm Signal
This display example shows that the buzzer will signal an alarm condition with an intermittent signal. The signal definitions are:
1 Continuous
2 Intermittent, one second on at two second intervals (default)
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, buzzer will not sound
3.3.8.3 Alarm Horn Signal
Figure 3-55 Horn Alarm Signal
This display example shows that the horn will signal an alarm condition with an intermittent signal. The signal definitions are:
1 Continuous
2 Intermittent, one second on at two second intervals (default)
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, horn will not sound
3.3.8.4 Alarm Strobe Signal
Figure 3-56 Strobe Alarm Signal
This display example shows that the strobe will signal an alarm condition with a continuous signal. The signal definitions are:
1 Continuous (default)
2 Intermittent, one second on at two second intervals
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, strobe will not flash
3.3.8.5 Warning Signal Summary
The warning signals are in response to one or more sensors indicating gas levels at or above the sensors’ configured warning level.
Figure 3-57 Warning Signals
This display example shows that warnings are signaled by the internal Buzzer only.
3.3.8.6 Warning Buzzer Signal
Figure 3-58 Buzzer Warning Signal
This display example shows that the buzzer will not signal a warning condition. The signal definitions are:
1 Continuous
2 Intermittent, one second on at two second intervals
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, buzzer will not sound (default)
3.3.8.7 Warning Horn Signal
Figure 3-59 Horn Warning Signal
This display example shows that the horn will not signal a warning condition. The signal definitions are:
1 Continuous
2 Intermittent, one second on at two second intervals
3 Double tap, two beeps at 5 second intervals
4 Triple tap, three short beeps at 15 second intervals
5 Off, horn will not sound (default)