Specifications

26
Once the current password has been entered, the panel will prompt for the configuration parameter being changed.
If the password has been lost:
1. Power down the DVP-120
2. RemovetheJumperShortingConnectorfromtheEXTheaderandplacetheJumperShortingConnectorontothetoptwopinsoftheSYSheader.
3. Power up the DVP-120. The first display is the current password on the unit.
4. RemovetheJumperShortingConnectorfromtheSYSheaderandinstallbackontothetwobottompinsoftheEXTheader.
2. Configure Sensors Submenu
4.8 See Section 3.1 Initial Operating Mode for more detail
4.9 See Section 3.1.2 User Interface for more detail
4.10 See Section 3.3 Setting the System Configuration for more detail
4.11 See Section 3.3.3 Configure Sensors Submenu for more detail
Press Menu to display Hardware Summary
x 2 Configure Sensors
Sensor
Figure 4-6 Sensor Summary
Sensor type (set sensor type)
1=CO,2=NO2,3=Combustible,0=None
Figure 4-7 Sensor Type
AlarmLevel-setlevelifneeded,0=disable
Figure 4-8 Sensor Alarm Level
Warning Level - set level if needed
Figure 4-9 Sensor Warning Level
Sensor Range - default range is in system
Figure 4-10 Sensor Range
Next Sensor - complete for all sensor channels
3. Configure Relays, Horn & Strobe Submenu
4.12 See Section 3.3.4 Configure Relays, Horn & Strobe Submenu for more detail
Press Menu to display Hardware Summary
x 3 Configure Relays
Relay 1
Figure 4-11 Relay Summary
Default - Normally Off
Figure 4-12 Relay Mode
Default - Delay – 1 Minute
Figure 4-13 Turn On Delay