Specifications

27
Default - Minimum Runtime - 1 Minute
Figure 4-14 Minimum on Time
Relay 2 - repeat for all relays, horn and strobe
4. Configure Zones Submenu
4.13 See Section 3.3.7 Configure Zones Submenu for more detail
Definitions:
Zone – Defines Sensor Input & Relay / Alarm Output
Group – Set of Sensors of same type and output within the same zone.
Average – Activation based upon an average of sensors in a group
Voting – Number of sensors needed to be above trip point to activate output
Quorum–Numberofsensorsneedtovote,1=anysensor.
Press Menu to display Hardware Summary
x 4 Configure Zones
Zone 1 Controls
R_ R_ R_ H_ S_
Enter (underlined) number of output for zone
R=Relay(1,2and3),H=Horn(4),S=Strobe(5)
Figure 0-36 Zone Controls
Z one 1 Cont rols
R1 R2 R3 H4 S5
_____
Figure 4-15 Zone Controls
Configure Group 1
Sensor type - enter #
1=CO,2=NO2,3=Combustible,0=None
Figure 4-16 Zone Group Type
Sensor Number - enter a two digit number for each sensor to be included in the group (e.g., 01, 02, 03…12.) from 01 through 12.
Figure 4-17 Sensor Selection
Rising (activation) Trip Point
Figure 4-18 Rising Trip Point Entry
The default rising Trip Points are:
- Carbon Monoxide 35ppm
- Nitrogen Dioxide 2.5ppm
- Combustible5%LEL
Falling (off) Trip Point
Figure 4-19 Falling Trip Point Entry
The default falling Trip Points are:
- Carbon Monoxide 15ppm
- Nitrogen Dioxide 1.2ppm
- Combustible3%LEL