Operation Instructions
Table Of Contents
- 1 General Safety Information
- 2 Use Instructions and Limitations
- 3 Installation Instructions
- 3.1 Location & Mounting
- 3.2 Installation
- 3.2.1 General Wiring Information
- 3.2.2 Installation Diagram
- 3.2.3 Power Connection
- 3.2.4 Remote Sensor Connection
- 3.2.4.1 MRS-485 Connection and Operation
- 3.2.4.2 Connection
- 3.2.4.3 Dip Switches and Addressing
- 3.2.4.4 Topology
- 3.2.4.5 Line Termination – End of Line Resistor
- 3.2.4.6 Baud Rate
- 3.2.4.7 Wire Selection
- 3.2.4.8 Wire Length
- 3.2.4.9 Grounding
- 3.2.4.10 External Power Supply
- 3.2.4.11 Power Wire
- 3.2.4.12 4-20mA Connection
- 3.2.4.13 Relay Connection
- 3.2.5 Remote Relay Connection
- 3.2.6 Remote Relay Operation
- 3.2.7 Horn & Strobe Connection
- Figure 3-4 – System Wiring Diagram
- 4 Operations
- 4.1 Power up
- 4.2 User Interface
- 4.3 Normal Status Display
- 4.4 ALARM, WARNING, and TROUBLE Status Display
- 4.5 Ventilation Control
- 4.6 Main Menu
- Figure 4-6 –
- 4.6.1 CONFIGURE SYSTEM?
- 4.6.2 MANUAL CONFIGURE?
- 4.6.3 CONFIGURE RELAYS, H/S, BUZZER?
- 4.6.4 COMMUNICATION?
- 4.6.5 VIEW SENSORS?
- 4.6.6 DATE/TIME – PASSWORD?
- 4.6.7 EVENTS?
- 4.6.8 TECHNICAL SUPPORT?
- 5 BACnet
- 5.1 General Information
- Table 5-1 – Types of Detector
- Table 5-2 – Engineering Unit
- Table 5-3 – BACnet Objects for Group Settings of all Zone
- Table 5-4 – BACnet Object for Detector Reading
- Table 5-5 – Bit Assignment for Zone[N]. mode value
- Table 5-6 – BACnet Objects for Zone Configuration
- Table 5-7 – BACnet Objects for DVP-1200 Outputs
- 5.1 General Information
- 6 Testing & Maintenance
- 7 Appendix A – Table of Figures
- 8 Appendix C – Replacement Parts
- 9 Appendix D – Setup Record
- 10 Macurco Gas Detection Product limited warranty
- Blank Page
- Blank Page
- Blank Page
Macurco
TM
DVP-1200 Manual
REV – 1.3.1 [34-8708-4770-7 ] 11 | Page
3.2.3 Power Connection
The main power cable should be routed into the bottom left conduit entry.
Macurco recommends a minimum wire size of 18 AWG and the wire insulator must be rated for at least 140°F (60°C) service.
The power connector will accept wire from 12-24 AWG.
The safety ground wire should be connected to terminal labeled as GND. Connect the wires to the following terminals:
Signal
Connector Label
Pin Label
Line (120/220/240/250 VAC)
AC~
L
Neutral
AC~
N
Ground
AC~
GND
Table 3-2 –
1. The line, neutral and ground wires should be stripped 1/4 in. (6.5 mm).
2. Press down the white button of the connector. You can use flat-headed screwdriver for this.
3. Insert the bare wire into the respective wire cavity of the connector. Refer Table 3-2.
4. Release the white button.
5. Ensure that the wire cannot be easily pulled from the connector.
Figure 3-4 – System Wiring Diagram
2