3.2.3 Power Connection
The main power cable should be routed into the bottom left conduit entry.
Macurco recommends a minimum wire size of 18 AWG and the wire insulator must be rated for at least 140°F (60°C) service.
The power connector will accept wire from 12-24 AWG.
The safety ground wire should be connected to terminal labeled as GND. Connect the wires to the following terminals:
Signal
Pin Label
Line (120/220/240/250 VAC)
L
Neutral
N
Ground
GND
Table 3-2
1. The line, neutral and ground wires should be stripped 1/4 in. (6.5 mm).
2. Press down the white button of the connector. You can use flat-headed screwdriver for this.
3. Insert the bare wire into the respective wire cavity of the connector. Refer Table 3-2.
4. Release the white button.
5. Ensure that the wire cannot be easily pulled from the connector.