REV 1.3.1 [34-8708-4770-7 ] 33 | Page
Figure 4-21
If a horn/strobe is already assigned as a dedicated alarm, warning, or trouble (see Section 4.6.1.2.2.3 CONFIGURE H/S), it will
not be able to be added to the zone configuration and vice-versa. In the example below, H/S 1 has already been assigned as a
dedicated alarm. Attempting to add it to the Zone 1 configuration results in an error message. Similarly, if a Horn/Strobe is
assigned to a zone then it cannot be assigned to alarm, warning, or trouble.
Figure 4-22
4.6.2.4 GROUP CONFIG.
Menu path: Main Menu-->CONFIGURE SYSTEM? -->MANUAL CONFIGURE? -->CONFIGURE ZONES? -->ADD/EDIT ZONES-->GROUP
CONFIG. -->
Each group of sensors can be configured with settings unique to each zone.
For example, Group 1 sensors (CO gas) ALARM could be set to 200ppm in Zone 1 and 100ppm in Zone 2.
To configure the sensor groups within each zone, select GROUP CONFIG. from the zone configuration menu and press ENTER. To
view or change values for a sensor type, select SENSOR TYPE and press ENTER.