Operation Instructions
Table Of Contents
- 1 General Safety Information
- 2 Use Instructions and Limitations
- 3 Installation Instructions
- 3.1 Location & Mounting
- 3.2 Installation
- 3.2.1 General Wiring Information
- 3.2.2 Installation Diagram
- 3.2.3 Power Connection
- 3.2.4 Remote Sensor Connection
- 3.2.4.1 MRS-485 Connection and Operation
- 3.2.4.2 Connection
- 3.2.4.3 Dip Switches and Addressing
- 3.2.4.4 Topology
- 3.2.4.5 Line Termination – End of Line Resistor
- 3.2.4.6 Baud Rate
- 3.2.4.7 Wire Selection
- 3.2.4.8 Wire Length
- 3.2.4.9 Grounding
- 3.2.4.10 External Power Supply
- 3.2.4.11 Power Wire
- 3.2.4.12 4-20mA Connection
- 3.2.4.13 Relay Connection
- 3.2.5 Remote Relay Connection
- 3.2.6 Remote Relay Operation
- 3.2.7 Horn & Strobe Connection
- Figure 3-4 – System Wiring Diagram
- 4 Operations
- 4.1 Power up
- 4.2 User Interface
- 4.3 Normal Status Display
- 4.4 ALARM, WARNING, and TROUBLE Status Display
- 4.5 Ventilation Control
- 4.6 Main Menu
- Figure 4-6 –
- 4.6.1 CONFIGURE SYSTEM?
- 4.6.2 MANUAL CONFIGURE?
- 4.6.3 CONFIGURE RELAYS, H/S, BUZZER?
- 4.6.4 COMMUNICATION?
- 4.6.5 VIEW SENSORS?
- 4.6.6 DATE/TIME – PASSWORD?
- 4.6.7 EVENTS?
- 4.6.8 TECHNICAL SUPPORT?
- 5 BACnet
- 5.1 General Information
- Table 5-1 – Types of Detector
- Table 5-2 – Engineering Unit
- Table 5-3 – BACnet Objects for Group Settings of all Zone
- Table 5-4 – BACnet Object for Detector Reading
- Table 5-5 – Bit Assignment for Zone[N]. mode value
- Table 5-6 – BACnet Objects for Zone Configuration
- Table 5-7 – BACnet Objects for DVP-1200 Outputs
- 5.1 General Information
- 6 Testing & Maintenance
- 7 Appendix A – Table of Figures
- 8 Appendix C – Replacement Parts
- 9 Appendix D – Setup Record
- 10 Macurco Gas Detection Product limited warranty
- Blank Page
- Blank Page
- Blank Page
Macurco
TM
DVP-1200 Manual
REV – 1.3.1 [34-8708-4770-7 ] 40 | Page
4.6.3.2 CONFIGURE REMOTE RELAYS
Menu path: Main Menu-->CONFIGURE SYSTEM? -->MANUAL CONFIGURE? -->CONFIGURE RELAYS, H/S, BUZZER? -->CONFIGURE
REMOTE RELAYS?
To configure remote relays, follow the menu as shown in the images below. The user must first select DISCOVER REMOTE
RELAYS before ASSIGN AND CONFIGURE REMOTE RELAYS becomes selectable.
Figure 4-35 –
Once the system has found remote relay, the screen shown in Figure 4-36 below will be display with address of remote relay. If
DVP-1200 does not find any remote relay, then it will display NO RELAY FOUND in bottom box of the LCD. In this case it is
recommended to verify the communication settings for Remote Relay in DVP-1200 matches with RR-24 unit in addition to
verifying the wiring between RR-24 and DVP-1200.
Figure 4-36 –
After successful remote relay discovery, next step is to assign and configure remote relay. Relays 9 to 12 in DVP-1200 are
reserved for remoted relays. Odd number relay (9 and 11) correspond to Relay 1 of the remote relay (RR-24) and even number
relay (10 and 12) correspond to Relay 2 of the remote relay (RR-24). Remote relays can only be assigned to continuous relay
number i.e. a remote relay can be assigned either Relay 9 and 10 or Relay 11 and 12. If only one remote relay is connected, then
DVP-1200 will only allow to assign the connected remote relay to Relay 9 and 10. Follow the menu sequence as shown below to
assign remote relay.