Default Configuration – Factory Settings
The default Power Up Test setting is On
The default Display setting is Off
The default Buzzer setting is Off
The default Alarm Relay Setting is activation at 5.0 ppm
The default Alarm Relay Configuration is Normally Open
The default Fan Relay Setting is activation at 2.5 ppm
The default Fan Relay Delay setting is 3 minutes
The default Fan Relay Runtime setting is OFF
The default Fan Relay Latching condition is OFF
The default Trouble Fan Setting condition is OFF
The default 4-20mA Output setting is OFF
To change settings, remove the Philips screw on the front of the TX-12-ND. Pull off the front cover of the unit.
Selecting Default Configuration – “dEF”
To select the Default Configuration, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push the
Enter button to enter the Con menu. The first selection is the “dEF” or Default setting. Push Enter. If it is already in Default
configuration, there will be no action. If it is not already in Default configuration, “nO” will be displayed. Push Next to change it to “YES”
(flashing) then push Enter to confirm the change (solid) and push Enter again to return to “dEF” in the con menu. Push Next until “End”
is displayed then push Enter to get back to normal operation.