Owners Manual

© 2015 Sensata Technologies 11
Installation
2.3 Wiring the Inverter – General Requirements
This section describes the requirements and recommendations for wiring a
CMW Series inverter. Before wiring the inverter, carefully read all instructions.
WARNING: Wiring should meet all local codes/standards and be
performed by quali ed personnel (i.e., licensed electrician).
2.3.1 Wiring Requirements
All conductors that are at risk for physical damage must be protected by
tape or placed in a raceway.
Always check for existing electrical, plumbing, or other areas of potential
damage prior to making cuts in structural surfaces or walls.
Where DC wiring must cross AC or vice-versa, try to make the wires at
the crossing point perpendicular (90 degrees) to one another.
DC overcurrent protection must be provided as part of the installation.
Use only copper wires with a minimum temperature rating of 75°C
(194°F).
2.3.2 Torque Requirements
All wiring to the DC terminals and DC ground connection should be checked
periodically (once a month) for proper tightness. For the torque requirements,
refer to Table 2-1. If you don’t have a torque wrench, ensure all connections
are tight.
Table 2-1, DC Terminal – Torque Requirements
Inverter
Model
DC
Terminals
Torque
Requirements
Torque Wrench
Size Needed
CMW412
Hex Cap
screws
52 to 58 lbf-in
(5.9 to 6.5 N-m)
NA
CMW1012
M6 x 1.0
Hex nuts
79 to 96 lbf-in
(8.9 to 10.9 N-m)
10 mm wrench
CMW1512
M8 x 1.25
Hex nuts
16 to 21 lbf-ft
(22 to 28 N-m)
13 mm wrench
2.4 DC Wiring
This section describes the inverter’s required DC wire sizes, the recommended
disconnect/overcurrent protection, and how to make the DC connections to
the inverter and the battery bank.
WARNING: Even though DC voltage can be regarded as “low
voltage”, signifi cant hazards may be present, particularly from short
circuits of the battery system.
CAUTION: The inverter is NOT reverse polarity protected—which
means if the negative and positive battery voltage is connected to
the inverter backwards, the inverter will likely be damaged. Use
a voltmeter to verify the correct polarity BEFORE connecting the
DC wires.
CAUTION: DO NOT connect the battery cables to the inverter until
all wiring is complete, and the correct DC voltage and polarity have
been verifi ed.