Owner`s manual
© 2010 Magnum Energy, Inc.Page 26
3.0 Installation
Figure 3-11, DC Connections - without Magnum Inverter Installed
Inverter DC Negative Connection
Inverter DC Positive Connection
Battery Negative Connection
3
6
1
2
4 5
3 6
1 2
4
5
3
1
2
4
B attery P ositive C onnection
3
1
2
4
BATTERY NEGATIVE CONNECTION
INVERTER DC NEGATIVE CONNECTION
BATTERY POSITIVE CONNECTION
INVERTER DC POSITIVE CONNECTION
Top of Shunt
hardware stack-up:
1
DC Shunt
2
Negative (-) Inverter Cable Lug
3
DC Negative (-) Busbar Cable
4
Brass Flat washer
5
Brass Split-lock washer
6
Brass Hex Bolt (3/8-16)
DO NOT place anything between
the DC shunt and the negative
inverter cable lug.
Bottom of DC Breaker
hardware stack-up:
1
DC Breaker Terminal
2
Positive (+) Battery Cable Lug
3
Split-lock washer
4
Hex Bolt (3/8-16)
DO NOT place anything between
the DC breaker terminal and the
positive battery cable lug.
Bottom of Shunt
hardware stack-up:
1
DC Shunt
2
DC Neg. to Ground Busbar
3
Negative (-) Battery Cable Lug
4
Brass Flat washer
5
Brass Split-lock washer
6
Brass Hex Bolt (3/8-16)
DO NOT place anything between
the DC shunt and the busbar
or between the busbar and the
negative battery cable lug.
Top of DC Breaker
hardware stack-up:
1
DC Breaker Terminal
2
Positive (+) Inverter Cable Lug
3
Split-lock washer
4
Hex Bolt (3/8-16)
DO NOT place anything between
the DC breaker terminal and the
positive inverter cable lug.