1.0 Safety Information
1.0 Safety Information
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important safety instructions that must be followed during the installation
and operation of this product. Before using the Mini Magnum Panel (MMP), read all instructions
and cautionary markings on: (1) the MMP Enclosure, (2) the inverter/charger, and (3) the batteries
in this manual as well as the individual manuals provided for each component of the system.
These installation instructions are for use by quali ed personnel only. Do not perform any
installation or servicing other than that speci ed in this Owner’s manual unless you are quali ed
to do so. Incorrect installation or servicing may result in a risk of electric shock, re, or other
safety hazard.
1.1 Safety Symbols
The following safety symbols have been placed throughout this manual to indicate dangerous
conditions and important safety instructions.
WARNING: This symbol indicates that failure to take a speci ed action could result in
physical harm to the user.
CAUTION: This symbol indicates that failure to take a speci ed action could result in
damage to the equipment.
Info: This symbol indicates information that emphasizes or supplements important
points of the main text.
1.2 General Safety
All electrical work must be performed in accordance with local and national electrical codes.
This product is designed for indoor/compartment installation. It must not be exposed to rain,
snow, moisture or liquids of any type.
Use insulated tools to reduce the chance of electrical shock or accidental short circuits.
Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing
maintenance on the inverter.
Both AC and DC overcurrent protection must be provided as part of the installation.
Use Class 1 wiring methods for eld wiring connections to terminals of a Class 2 circuit.
Listed or labeled equipment shall be installed and used in accordance with any instructions
included in the listing or labeling.
To reduce risk of electric shock, disconnect all wiring before attempting any maintenance or
cleaning. Turning off the inverter will not reduce this risk, the inverter bypass must be used or
the panel should be totally disconnected from all sources.
All wiring must have a minimum rating of 300V, 75°C. AC wiring must be no less than 10 AWG
(5.3 mm
2
) gauge copper wire. Battery cables should be no less than #4/0 AWG for 12 and
24 volt systems and #2/0 AWG gauge for 48 volts systems. Crimped and sealed copper ring
terminal lugs with a 3/8 hole should be used to connect to the DC terminals inside the MMP
enclosure. Soldered cable lugs are also acceptable.
Torque all AC wiring connections and DC cable connections to the required torque values.
READ AND SAVE THESE INSTRUCTIONS