3.0 Installation
3.15 Functional Test
After all electrical connections from the MMP enclosure to the inverter, batteries, AC source, and
sub-panel have been completed; follow these steps and refer to Figure 3-28 to test the installation
of the MMP enclosure and verify proper operation of the BYPASS switch breakers.
WARNING: During this Functional Test, the front cover is removed and exposes
personnel to potential dangerous voltages and shock hazards inside the MMP enclosure
that may cause damage, injury, or death. If you do not have experience working with
AC and DC voltage circuits, do not attempt this test - use an experienced electrical
installer.
CAUTION: During this Functional Test, if any step cannot be veri ed or is incorrect,
stop and recheck/correct the connections before proceeding to the next step.
1. Turn OFF all AC breakers (i.e., INV BYP, INV IN and INV OUT) in the MMP enclosure.
CAUTION: Use a multimeter to verify the correct DC voltage for your particular inverter
model (i.e., 24-volt battery bank for a 24-volt inverter) and ensure the polarity of the
battery voltage is correct [battery positive (+) connected to the inverter positive terminal
thru the DC circuit breaker and battery negative (-) connected to inverter negative
terminal thru the DC shunt].
CAUTION: Prior to turning on the inverter, turn OFF all inverter loads in the Inverter
Load panel (i.e., sub-panel).
2. After verifying the proper battery bank voltage for your inverter and the battery cable
connections are the correct polarity, apply battery power to the inverter by turning the Inverter
DC disconnect breaker to the ON (up) position.
3. Turn the inverter ON.
a. Connect an AC voltmeter to the Inverter Output Terminals and verify the correct AC
output voltage of the inverter (depends on your inverter AC output voltage).
Info: If the inverter does not turn on - verify the DC connections to/from the inverter to
the battery, and/or refer to the Troubleshooting section for your particular inverter.
Info: If the inverter has a Search mode feature, the inverter’s AC full output voltage
will not be present/correct until Search is turned OFF, or by connecting a large enough
light bulb to bring the inverter out of Search. DO NOT connect anything but a light bulb
until all wiring and voltages are con rmed to be correct.
If using a Magnum inverter, use a light bulb greater than 5 watts (5 watts is the default
setting) to bring the inverter out of Search mode; or, the Search mode can be turned
OFF with a remote control (ME-RC or ME-ARC).
4. Turn ON the INV OUT
1
breaker(s) in the MMP enclosure.
a. Ensure the inverter AC output voltage is passing thru the INV OUT (Inverter Output) breaker
by verifying the correct output voltage is present on the AC Output Terminals.
5. Turn ON the INV BYP
2
breaker(s) in the MMP enclosure.
a. Ensure the inverter AC output voltage is no longer present on the AC Output Terminals.
6. Apply power from an external AC source (utility or AC generator) to the AC Input Terminals.
a. Connect an AC voltmeter to the Inverter Output Terminals and verify the AC voltage from
the external AC source is present. Move the AC voltmeter to the AC Output Terminals and check
that the AC source power is passing thru the INV BYP (Inverter Bypass) breaker by verifying
the AC source voltage present earlier is also present on the AC Output Terminals.