Appendix A - Optional Equipment and Accessories
A-4 Installing Optional DC Breakers
The MMP enclosure provides the room to install additional DC circuit breakers that may be used
for charge controllers, a PV-GFP device, and other DC loads. This enclosure has been specifi cally
designed to allow both back mounted (1” wide)
1
or DIN rail mounted (1/2” wide)
2
breakers.
CAUTION: Turning the Inverter DC Disconnect breaker off only removes the battery
power to the inverter, it does not interrupt power from the battery to the DC load
breakers. This must be accomplished by turning off the DC load breakers themselves.
Therefore, to shut the system off completely, all of the breakers in the MMP enclosure
should be switched to the OFF position.
To install optional DC breakers inside the MMP enclosure:
1.
Remove the front cover to the MMP enclosure.
2.
For DIN rail mounted breakers
(refer to Figure A-4a):
For back mounted type breakers
(refer to Figure A-4b):
a. Install the breaker(s) on the DIN rail mounting
track, and slide all the way to the left side.
b. Place the breaker(s) on the DIN rail track, and
slide a DIN rail clamp tight against the right side
of last circuit breaker; and tighten this clamp to
secure the breaker(s) on the DIN rail track.
c. For each breaker installed, remove only 1
knockout (= 1/2” slot) in the front cover.
a. Remove the DIN rail mounting track by
unscrewing the two #8, T15 Torx drive
screws holding this mounting track.
b. Secure the breaker(s) to the panel using
two #8 screws, minimum 1/2” length.
c. For each breaker installed, remove
only 2 knockouts (= 1” slot) in the front
cover.
3.
Ensure the breaker(s) align correctly into the spaces made by the knockouts removed from
the front cover.
4.
Wire the breaker(s) to the DC circuit, use Figure A-4c to assist in wiring the breaker.
5.
Replace the MMP front cover and check that the breaker operates correctly.
Note 1 - For the 1/2” wide DIN rail mounted breakers, use Q-Frame types (QYN Series by CBI).
Note 2 - For the 1” back mounted breakers, use E-Frame types (E Series by Carling Technologies,
209 Series by Airpax/Sensata Technologies or CF Series by Heinemann/Eaton).
DIN RAIL
MOUNTING TRACK
DIN RAIL MOUNTED DC BREAKER
(½” WIDTH)
Figure A-4a, Installing DIN Rail Mounted DC Breakers
DIN RAIL MOUNTED DC BREAKER
(1/2” WIDTH)
DIN RAIL
MOUNTING TRACK