Appendix A - Optional Equipment and Accessories
Info: Make sure enough insulation is stripped so that the inverter’s AC input wire is
fully inserted in the AC terminal block and enough uninsulated wire is still available to
contact with the lightning arrestor wire when using the service entrance connector.
Info: Some readily used service entrance connectors are the Type SX manufactured
by Ilsco (www.ilsco.com), or the Type N manufactured by Thomas and Betts (www.
tnb.com).
Lightning
Arrestor
(DC rated)
Lightning
Arrestor
(DC rated)
Lightning
Arrestor
(AC rated)
TO PROTECT
DC INP UT TO
INVERTER
T O PROTECT
INP UT TO
DC LO ADS
TO PROTECT
AC INP UT TO
INVERTER
T O LIGHTNING
ARRESTOR
TO INVERTER
AC INP UT
AC
TERMINAL
BLOCK
SIDE VIEW
NOTE: CRIMP A RING TERMINAL
WITH A
5/16" OPENING TO THE
LIGHTNING ARRESTOR WIRES AND
CONNECT TO THE
MAGNUM
INVERTER
DC TERMINALS.
F
OLLOW THE PROPER DC
HARDWARE STACK AND ENSURE
THERE IS NOTHING BETWEEN THE
DC BUSBARS AND THE
INVERTER’S DC TERMINALS.
N
OTE: THE AC TERMINAL BLOCK IS NOT RATED TO
CONNECT MORE THAN ONE WIRE LARGER THAN
#12
AWG. T
HEREFORE TO CONNECT A LIGHTNING
ARRESTOR
, A SERVICE ENTRANCE CONNECTOR (OR
SPLIT BOLT
) IS REQUIRED TO CONNECT BOTH THE
INVERTER
’S AC INPUT WIRE AND THE LIGHTNING
ARRESTOR WIRE TO THE AC TERMINAL BLOCK.
E
NSURE THE SERVICE ENTRANCE CONNECTORS ARE
INSULATED FROM EACH OTHER TO PREVENT THE
AC
INPUT WIRES FROM SHORTING TO EACH OTHER.
S
ERVICE
ENTRANCE
CONNECTOR
(SPLIT BOLT)
Figure A-5b, Wiring Lightning Arrestor to MMP Enclosure