3. Installation, continued
AC Wiring
WARNING: De-energize all sources of power including batteries (DC), shore
power (AC), and AC generator (if applicable).
AC wiring must be performed by a qualified person or licensed
electrician.
DO NOT connect the inverters output to an AC power source.
WARNING: Risk of electric shock. Use only the ground-fault circuit
interrupter [receptacles(s) or circuit breaker(s)] specified in the
installation and operating instructions manual supplied with the
inverter. Other types may fail to operate properly when con
nected to this inverter equipment.
Ground-fault circuit interrupters must be installed in the
vehicles wiring system to protect all branch circuits.
CAUTION: DO NOT place AC cabling in the same conduit with DC cabling.
NOTE: Read all instructions and cautionary markings located at the beginning of this
manual and in the pre-installation section, before installing the inverter and
batteries.
The minimum wire size for all ME Series models must be #10 AWG. The
installer must provide the appropriate circuit protection for the wire size used.
Refer to appropriate electrical codes for wire sizing and circuit protection.
AC Input (Shore Power) Routing
Route a 30 amp service (shore power) to the inverter. If the installation includes a
generator, route a 30 amp service (shore power) to an approved selector switch and
then to the main AC panel.
AC Input (Generator) Routing
Route a 30 amp service (generator) to an approved selector switch and then to
the main AC electrical panel.
Main AC Electrical Panel Routing
Route the AC Output from the inverters internal terminal block to the 30 amp
breaker in the sub panel.
2. INSTALLATION
Table 4 - Recommended AC Wire Ratings for 120 VAC Applications
Inverter ME1512 ME2012 ME2512 ME3012
Power Rating 1500 VA 2000 VA 2500 VA 3000 VA
Input Breaker 30 A 30 A 30 A 30 A
Input Wiring #10 AWG #10 AWG #10 AWG #10 AWG
Output Wiring #10 AWG #10 AWG #10 AWG #10 AWG