3. Installation, continued
Wiring the Inverter AC Input (refer to diagrams on the following pages)
Remove the chassis AC access cover to access the internal terminal block.
Route the cable and conduit from the main panel, approved bypass selector
switch or main AC panel to the inverters AC INPUT conduit clamp. Tighten
the clamp securely on the conduit. Always leave a little extra slack in the wiring.
Connect the hot wire (BLACK) from the main panels dedicated 30 amp breaker to
the AC INPUT (HOT 1 IN) terminal. Tighten the screw terminal to 16 inch-pounds.
NOTE: If using dual inputs, connect the RED wire from the main panel to AC INPUT
(HOT 2 IN)
Connect the neutral (WHITE) from the main panels neutral bus bar to the AC
INPUT (NEU) terminal. Tighten the screw terminal to 16 inch-pounds.
Connect the ground (GREEN) wire from the main panels neutral bus bar to the
GROUND terminal. Tighten the terminal to 16 inch-pounds.
Wiring the Inverter AC Output (refer to diagrams on the following pages)
Route the cable and conduit from the AC distribution panel to the inverters AC
OUTPUT conduit clamp. Tighten the clamp securely on the conduit.
Connect the hot (BLACK) wire to the AC OUTPUT 1 (HOT) terminal. Tighten the
terminal to 16 inch-pounds.
NOTE: If using dual outputs, connect the RED wire to the AC OUTPUT 2 (HOT)
terminal.
Connect the neutral (White) wire to the AC OUTPUT (NEU) terminal. Tighten the
terminal to 16 inch-pounds.
Connect the ground (Green) wire to the GROUND terminal. Tighten the termi-
nal to 16 inch-pounds.
Final Inspection
Verify all cables / conduit runs are secured with wire ties or other nonconductive
fasteners to prevent chafing or damage from movement and vibration.
Verify strain reliefs or grommets are in place to prevent damage to the wiring or
conduit where it passes through walls, bulkheads or other openings.
Verify all AC connections are correct and torqued to 16 inch pounds.
Replace the covers on the main electrical / distribution panel.
Replace the chassis access cover.
Verify the inverters front panel switch is in the "OFF" position.
NOTE: If required by code, have the installation inspected by an electrical inspector.