5. Start-up and Test
Connecting the Batteries to the Inverter
After all electrical connections have been completed, connect the batteries to the
inverter to begin the start-up process.
CAUTION: Verify correct battery voltage and polarity before connecting the
cables to the inverter.
Replace the fuse or (close the breaker) at the DC disconnect.
Remove the electrical tape from the cable lugs and verify 12 VDC at the cable
connectors using a multimeter. Verify correct polarity: Black is negative (-); Red is
positive (+).
Connect the negative (BLACK) battery cable to the inverters negative terminal.
The cable lug must be flush to the terminals surface. Place a lock washer and nut
over the lug and torque the connection to 10 to 15 foot pounds.
NOTE: There may be a spark (and audible snap) when the cable lug first contacts the
inverters positive terminal. This is a normal condition.
Connect the positive (RED) battery cable to the inverters positive terminal. The
cable lug must be flush to the terminals surface. Place a lock washer and nut over
the lug and torque the connection to 10 to 15 foot pounds.
Verify all cables and connectors are properly secured.
Place the red and black terminal covers on the inverters DC connector. Secure
the covers with enclosed hardware.
If the batteries are in an enclosure, perform a final check of the hold down brack-
ets and all connections. Close and secure the battery enclosure.
Final Inspection and Power-up
Prior to starting the inverter, make sure all connected appliances are switched
OFF or disconnected from the AC receptacles.
Use a multimeter to verify 12 VDC at the inverters DC connectors.
Switch the inverter power switch to ON. The inverters LED will flash indicating
DC power and the start-up sequence.
NOTE: When using the remote control, the inverters ON/OFF switch is disabled in
Charge mode.
Verify the breakers on the distribution panel are switched ON.
Use a true RMS multimeter to verify 120 VAC at the coachs AC outlets.
Connect the inverter to shore power and switch the main circuit breaker ON.
Verify the inverters LED switches from INVERTER to AC IN (SHORE POWER).
Use a true RMS multimeter to verify 120 VAC at each of the coachs AC outlets.
Switch the Shore Power OFF. Verify the inverters LED switches to inverter mode.