Using a PT Controller: Operation/Monitoring
Table 10-1, PT Default Settings on ME-ARC
Menu Items Default Settings
Battery Type Flooded
Absorb Done Time = 2.0 Hrs
Max Charge Rate 100%
Max Charge Time 12.0 Hrs
Bulk Start
Daily/SunUp = YES
Volts = 12.0 (12V), 24.0 (24V), 48.0 (48V)
SOC = 80%
PT Aux Relay
Engage Volts = 10.0 (12V), 20.0 (24V), 40.0 (48V)
Engage Delay = 10 Sec
Disengage Volts = 14.0 (12V), 28.0 (24V), 56.0 (48V)
Disengage Delay = 10 Sec
PT Alarm
Alarm ON Volts = 10.0 (12V), 20.0 (24V), 40.0 (48V)
Alarm ON Delay = 10 Sec
Alarm OFF Volts = 14.0 (12V), 28.0 (24V), 56.0 (48V)
Alarm OFF Delay = 10 Sec
PowerSave PT Display 15 Min
First screen – The top line displays the PT fault condition. The bottom line displays the fault his-
tory number (ex. H1), day(s) since this fault occurred, and the time that this fault occurred.
Continue to rotate the SELECT knob to display subsequent screens (bottom lines) for this fault.
Second screen – Displays the PT’s operational status at the time of this fault.
Third screen – Displays the PT’s power status at the time of this fault.
Fourth screen – Displays the PT’s relay status at the time of this fault.
Fifth screen – Displays the battery’s voltage and the battery’s amperage at the time of this fault.
Sixth screen – Displays the voltage of the PV array at the time of this fault.
Seventh screen – Displays the temperature of the PT’s BTS at the time of this fault.
Eighth screen – Displays the temperature of the PT’s FETs at the time of this fault.
Ninth screen – Displays the temperature of the PT’s internal inductors at the time of this fault.
Continue to rotate the SELECT knob to display earlier faults (as applicable).
Figure 10-4, PT Fault History Screens
Time fault
occurred
HiBatt Temp -PT
H1 D– 1 12:23A
HiBatt Temp -PT
H1 No Power Out
HiBatt Temp -PT
H1 Bulk Charging
Fault history
number
Day(s) since
fault occurred
PT Charge Status
at time of fault
Power Status at
time of fault
PT fault
Battery voltage
at time of fault
HiBatt Temp -PT
H1 Engage
HiBatt Temp -PT
H1 11.2V 11.6A
Relay Status at
time of fault
Battery amperage
at time of fault
BTS temp at
time of fault
PV array voltage
at time of fault
FETs temp at
time of fault
Inductor temp
at time of fault
HiBatt Temp -PT
H1 Ind: 83F
HiBatt Temp -PT
H1 FETs: 78F
HiBatt Temp -PT
H1 BTS: 130F
HiBatt Temp -PT
H1 142 VDC