Installation Manual

Using an ACLD: Monitoring
Page 118
© 2017 Sensata Technologies
Figure 11-1, ACLD METER Menu Map
11.2.2 ME-ARTR Router’s ACLD-speci c TECH Menus
Press the ME-ARTR’s TECH button, and rotate the SELECT knob to access:
TECH: 01 Temperature (rotate SELECT knob until ACLD Temperature displays)
• 01E ACLD Temperature – Displays temperature of the ACLD load diversion controller
plugged into the NETWORK port on the inverter (per METER: 06C ACLD Temperature display).
TECH: 02 Versions/TECH: 03 AccPort Versions rotate the SELECT knob to the port to which
the AGS is connected.
• #.# – Displays the software version of the ACLD connected to the Magnum network (displays
0.0” if the router does not sense an ACLD).
11.2.3 ACLD Menu Maps
The diagram below is a complete overview of the ACLD information displays available from the
ME-ARTR router’s METER button ACLD menu. Refer to Appendix A in the back of this manual for
a glossary of abbreviations that may appear on the router’s LCD display.
R
06D Target VDC/ 72F
1 13.3 2 ---- 3 ----
4 ---- 5 ---- 6 ----
ALL Read ACL METER
06E ACLD-40 Version:
1 #.# 2 ---- 3 ----
4 ---- 5 ---- 6 ----
ALL Read ACL METER
06A ACLD Status
1 SFlt 2 ---- 3 ----
4 ---- 5 ---- 6 ----
ALL Read ACL METER
06B Pwr Divert (kW)
1 #.# 2 ---- 3 ----
4 ---- 5 ---- 6 ----
ALL Read ACL METER
06C ACLD Temperature
1 72F 2 ---- 3 ----
4 ---- 5 ---- 6 ----
ALL Read ACL METER
04 AGS Meters
05 BMK Meters
06 ACLD Meters
ALL Select METER
P
R
R
R
R
ALL Ports METER Displays:
PORT
R
06A ACLD Status
Active - Float
P1A Read ACL METER
06B ACLD Power
Diverted: #.# kW
P1A Read ACL METER
ACLD Controller
Standby - Float
13.3V/ 72F #.#kW
P1A ACL Home
R
R
R
Port-specific METER Displays:
METER
METER
06C ACLD Temperature
88F
P1A Read ACL METER
06D Target Volts /
Battery Temperature:
13.3 VDC / 72F
P1A Read ACL METER
06E ACLD-40 Version:
Rev #.#
P1A Read ACL METER
R
Note: The ACLD must be connected and communicating with the
ME-ARTR for the ACLD displays to appear. If no ACLD is connected,
then NO ACLD Present” displays.
Active - Absorb Standby - Absorb High VAC In (2)
Active - Bulk Standby - Bulk No Load (4)
Active - Float Standby - Float Output Short (8)
Inactive Desat Fault (5) Overcurrent (7)
No Comm (10) High Current (1) Overtemp (9)
(#) – the
number of
identifying blinks
by the FAULT
LED on the ACLD
Available ACLD Statuses/Faults: