Installation Manual

Using a PT Controller: Operation/Monitoring
Page 140
© 2017 Sensata Technologies
05 BMK Setup
06 RC Setup
07 PT Setup
ALL Select SETUP
SETUP
07A Battery Type x7
LINKED
SYS Read PT SETUP
P
Note:Custom” must be
selected from the 07A Battery
Type menu in order to access
the two displays below.
P R
Set Battery Type x7
Flooded
SYS View PT SETUP
GEL, Flooded,
AGM1, AGM2
CC/CV,Custom
Custom Chg Settings
EQ Volts 28.0V
EQ Time 4.0Hrs
SYS edit PT SETUP
Note:CC/CV must be selected from the 07A Battery Type menu
in order to access the displays in this section.
Note: If CV Charge Done is set toHold CV Chg Volts”, CV Charge
mode will not end and no additional CC/CV screens display.
P
Note:CC/CV Controlled
displays (as above) when
CC/CV” has been selected
as the battery type in the 07B Battery Type menu. This
means that no changes can be made to this menu.
07B Absorb Done
CC/CV Controlled
SYS View PT SETUP
07C Max Charge
Rate = 100%
Time = OFF
SYS View PT SETUP
07B Absorb Done x7
Time = 2.0 Hours
SYS View PT SETUP
Time = 0.1-25.5 Hrs
Amps = 0-250 ADC
SOC = 50%-100%**
Rate = 0%-100%
Time = OFF, 0.1-25.5
07D Bulk Start
Daily/SunUp = YES
Low VDC = 20.0V
SYS View PT SETUP
Daily/SunUp = YES, NO
Low VDC = 18.0-32.0
SOC = OFF, 50-100%**
RR
Set Max CC/CV Charge
Time = 12.0 Hrs
SYS edit PT SETUP
Set CV Charge Done
Time = 2.0 Hrs
SYS edit PT SETUP
Set DC Volts to
Recharge = 24.0V
SYS edit PT SETUP
CC/CV Chg Settings
Max Chg Rate = 100%
CV Chg Volts =27.6V
SYS edit PT SETUP
CC/CV Chg Settings
CV Chg Done Time
SYS edit PT SETUP
Set CV Charge Done
Amps = 20 ADC
SYS edit PT SETUP
CV Chg Done Time
CV Chg Done Amps
Hold CV Chg Volts
P
P
P
P
P
P
OFF,0.1-25.5 Hours
24.0-32.0V (24v)
Rate = 0-100%
Volts = 24.0-32.0 (24v)
Custom Chg Settings
Absorb Volts 24.0V
Float Volts 26.4V
SYS edit PT SETUP
P
Volts=24.0-32.0 (24v)
Volts=24.0-32.0 (24v)
Time=0.1-25.5Hrs
P
x2
x2
R
R
** - Requires a connected BMK.
OR
Continued on next page.
Note: If “Linked” appears on
07A or 07B menus, refer to the
INFO on page 121 for details.
Figure 12-7, PT Charge Controller SETUP1 Menu Map