Owner`s manual

8.0 Using the ME-RC Remote
© 2012 Magnum Energy, Inc. 30
How long should I set the generator run time? This depends on whether
you are using the high temperature or low battery voltage autostart feature.
Using high temperature to autostart: When using the high tempera-
ture autostart feature, the generator autostarts and runs until the AGS:
04 Start Temp F setting is reached. This means you could set the time
to the lowest time setting (0.5 Hrs), knowing the generator will run until
the temperature setting is satis ed.
Using low battery voltage to autostart: When using the low bat-
tery voltage autostart feature, the generator run time is normally set to
help re-charge the batteries. Use the table below to help determine the
generator run time setting based on the 20-hour AH capacity of your
inverter’s battery bank.
Table 8-3, Battery AmpHrs Capacity to Suggested Gen Run Time
200 to 300 1 hour
310 to 500
510 to 700
710 to 900
910 to 1100
1110 to 1300
1.5 hours
2 hours
2.5 hours
3 hours
3.5 hours
4 hours1310 to 1500
1510 to 1700
1710 to 1900
1910 to 2100
2110 to 2300
2310 to 2500
4.5 hours
5 hours
5.5 hours
6 hours
6.5 hours
Battery
AmpHrs
Capacity
Suggested
Gen Run Time
Battery
AmpHrs
Capacity
Suggested
Gen Run Time
AGS: 04 Start Temp F Menu
This menu allows you to set and enable a temperature value that will cause
the generator to automatically start — to power an air conditioner (A/C) unit
for cooling — based on an increase in temperature, or by using an air condi-
tioning thermostat control.
Info: The optional ME-PT1 or ME-PT2 pigtail adapters can be used
to connect an air conditioner control circuit or a relay control circuit.
For more information, refer to the instruction sheet for each pigtail
adapter; either part number 64-0025 (ME-PT1 Instruction Sheet),
or 64-0026 (ME-PT2 Instruction Sheet).
This temperature autostart feature requires that the AGS’s remote tempera-
ture sensor cable (as shown in Figure 1-2) or an optional ME-PT1 or ME-PT2
pigtail adapter be connected to the REMOTE port on the AGS (see Figure
2-3). The location of the remote temperature sensor determines the area
being monitored for temperature. When the temperature around the remote
temperature sensor (based on the AGS: 08 AGS TECH menu’s Temp display)
increases to the AGS: 04 Start Temp F setting, the generator automatically
starts and runs based on the AGS: 03 Run Time Hour setting. When this run
time period is nished, the temperature sensor reading is checked. If the
AGS: 03 Run Time Hour Menu
This menu provides the settings that determine the length of time the gen-
erator will run once it has been autostarted by the AGS.
Default setting: Run Time = 2.0 Hrs
Range: 0.5 Hrs - 25.5 Hrs (0.5 hr increments)