10.0 Using the ME-RTR Router
METER: 03A AGS Status Menu
This read-only menu displays the AGS’s current status. There are 26 differ-
ent status messages to identify what state the AGS is currently in – only one
displays at any one time (refer also to Figure 10-2).
METER: 03B DC Volts-AGS Menu
This read-only menu displays the DC voltage measured at Terminals #3 and
#4 of the AGS module. This menu is useful in setting up the voltage start for
the AGS, and for troubleshooting its operation.
Info: The DC voltage reading in this menu may vary from the DC
voltage readings in the METER button’s 01A DC Volts and 04C DC
Volts-BMK menus. When troubleshooting, read the appropriate re-
lated meter for each device. When troubleshooting the AGS, use the
03B DC Volts-AGS menu for verifi cation and testing purposes.
Available statuses are (see Tables 11-1 thru 11-3 for information on each):
Info: This menu is important when determining if the AGS is work-
ing correctly, or for troubleshooting an AGS installation. For any
fault mode displayed in the status menu, refer to Section 12.0 in
this manual.
METER: 03C Gen Run Time Menu
This read-only menu displays the length of time the generator has been
running since it was autostarted by the AGS. This is useful when trying to
determine how long the generator has been running since it was autostarted
– in case you were not present when it started. This menu is enabled when
the CTRL: 03 Gen Control menu is set to AUTO, but does not display run
time when the generator has been manually started. Cooldown and warm-up
times are not included in this gen run time display.
• AC In
• Gen Cooldown
• Gen Warm-up
• Manual Run
• No Comm
• Off
• Quiet Time
• Ready
• Start Amp
• Start Exercise
• Start SOC
• Start Temp
• Start Test
• Start Time
• Start Topoff
• Start VDC
• Gen Run Fault
• Fault Amp
• Fault Exercise
• Fault MaxRn
• Fault SOC
• Fault Temp
• Fault Test
• Fault Time
• Fault Topoff
• Fault VDC
Info: The Gen Run Time menu’s timer is started when the gen run
sense voltage/signal is correct and qualifi ed at the AGS module. It is
not considered qualifi ed until after a full start attempt and the Gen
Warm-up Time setting is satisfi ed. Cooldown and warm-up times are
not included in the gen run time display. Total generator run time =
Gen Run Time + Gen Warm-up Time + Gen Cooldown.
Info: The times in this display are shown in tenths of an hour (0.0
hrs., 0.1 hrs., etc.,) – thus, 0.1 hrs. = 6 minutes.
Info: The Gen Run Time display resets to 0.0 each time the genera-
tor is autostopped. This meter is not designed to replace the hour
meter for total hours the generator has run.