Installation Manual

© 2014 Magnum Energy, Inc.Page 83
Using an AGS Module: Operation/Monitoring
7.2.6.2 AGS Remote Start Statuses
The following “Start” statuses identify the condition that autostarted the generator. If you deter-
mine that the autostart condition occurred sooner than expected (or didn’t want this autostart
condition), refer to the Section 7.1 “Setting Up the AGS using the ME-ARC” to change (or defeat)
the autostart setting.
Status Description
Start Amp Generator has autostarted based on the SETUP: 04C Gen Run Amps set-
ting.
Start Exercise Generator has autostarted based on the SETUP: 04H Gen Exercise setting.
Start SOC Generator has autostarted based on the SETUP: 04D Gen Run SOC setting.
Start Temp Generator has autostarted based on the SETUP: 04E Gen Run Temp setting.
Start Test The AGS is in Test mode. Test mode may be started from the TEST button
located on the AGS.
Start Time Generator has autostarted based on the SETUP: 04B Gen Run Time setting.
Start Topoff Generator has autostarted based on the SETUP: 04G Quiet Time Topoff
setting.
Start VDC Generator has autostarted based on the SETUP: 04A Gen Run VDC setting.
Start 100% SOC Generator has autostarted based on the SETUP: 04K Gen 100% SOC Start
Days setting.
Table 7-4, AGS Remote Start Statuses
7.2.6.3 AGS Remote Fault Statuses
The following “Fault” statuses indicate that the generator wasn’t able to start based on an ex-
pected autostart condition. Refer to Section 7.3.3 “Resolving AGS Faults using the ME-ARC” for
help in diagnosing the problem.
Table 7-5, AGS Remote Fault Statuses
Status Description
Fault Amp Generator failed to autostart in Start Amps mode.
Fault Exercise Generator failed to autostart in Start Exercise mode.
Fault Gen Run Generator successfully started and ran for more than two minutes, but un-
expectedly stopped before the AGS could automatically stop the generator.
Fault MaxRn Generator turned off because the SETUP: 04F Max Gen Run Time setting
had been met. This fault can occur when: 1) an autostop parameter has
been met, but it did not stop the generator, or, 2) the autostop condition
exceeded the Max Gen Run Time setting.
Fault SOC Generator failed to autostart in Start SOC mode.
Fault Temp Generator failed to autostart in Start Temp mode.
Fault Test Generator failed to start in Test mode.
Fault Time Generator failed to autostart in Start Time mode.
Fault Topoff Generator failed to autostart in Start Topoff mode.
Fault VDC Generator failed to autostart in Start VDC mode.
Fault 100% SOC Generator failed to autostart in 100% SOC Start Days mode.