1,000W 12V Manual

© 2010 Magnum Energy, Inc.
AC Input Wiring
Your inverter has an AC transfer feature that passes the AC input
power to the inverter’s output. Connection to the AC input is made
by hardwiring from a distribution panel as described below:
1. Run an appropriately sized 2-conductor plus ground cable (from
the AC distribution panel) through the strain relief clamp on the AC
IN opening (Figure 3, Item 10). Refer to Table 4 for minimum wire
size and overcurrent protection required for the AC input wiring.
2. Remove about two inches of the insulating jacket from the AC
cable, and then separate the three wires and strip about 3/4” of
insulation from each wire.
3. Using approved AC wire connectors, connect the incoming Hot
In, Neutral In, and Ground wires to the MMS Series’ AC wires
colored black (HOT IN), white (NEU IN), and green (AC GROUND)
respectively.
4. After making the AC input connections, secure the AC input cable
by tightening the strain relief clamp.
The AC input wiring in the inverter is complete. Review all AC wiring
to ensure all connections are correct and secure.
Table 4, Minimum Wire Size to Circuit-breaker Size
All inverter AC input and output wiring is required to be protected by an
o
vercurrent protection device. Overcurrent protection must be provided
by fuses or circuit-breakers, and must be properly sized and rated for
the wire they are protecting and the appliances being powered.
Most inverter’s that are hardwired use a service/distribution panel
wired to the in
verter’s input (main panel), and a dedicated panel
between the inverter’s output wiring and the AC loads (sub-panel).
These systems use the circuit breakers provided in the panels as the
overcurrent protection and the AC disconnect. If fuses are used, then
separate AC disconnect switches will be needed.
Based on information from the NEC, Table 4 provides the minimum
AC wire size and the suggested breaker size based on the inverter
model. However, a larger wire size may be required because of volt-
age drop
. The AC wire sizes provided in this table assume using only
copper wire and a temper
ature rating of 75° C or higher. A minimum
of #14 AWG is required for all AC wiring.
Inverter
Model
AC Input AC Output
Input
Breaker
Minimum
Wire
Size
Suggested
Breaker
Size
Output
Breaker
Minimum
Wire
Size
Suggested
Breaker
Size
MMS1012 20 amps #12 AWG 20 amps 15 amps #14 AWG 15 amps
MMS1012
-G
20 amps #12 AWG 20 amps 15 amps #14 AWG 15 amps
22
2.0 Installation
http://www.wholesalesolar.com/