MS Series Pure Sine Wave Inverter/Charger Owner’s Manual
Disclaimer of Liability The use of this manual and the conditions or methods of installation, operation, use, and maintenance of the MS Series inverter/charger is beyond the control of Sensata Technologies. Therefore, this company does not assume responsibility and expressly disclaims liability for loss, damage, or expense whether direct, indirect, consequential or incidental that may arise out of or be any way connected with such installation, operation, use, or maintenance.
Safety Information IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS FOR THE MS SERIES INVERTER/CHARGER THAT SHALL BE FOLLOWED DURING THE INSTALLATION AND OPERATION OF THIS PRODUCT. Before using the MS Series, read all instructions and cautionary markings. Also, be sure to review the individual manuals provided for each component of the system. The installation instructions are for use by qualified personnel only.
Safety Information • • Overcurrent protection for the AC output wiring is not provided as an integral part of this inverter. Overcurrent protection of the AC output wiring must be provided as part of the system installation. Refer to Section 2.5 “AC Wiring” for more information. The AC output neutral conductor and the DC negative conductors are not connected (bonded) to the inverter chassis. Both the input and output conductors are isolated from the enclosure and each other.
Safety Information CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DE IMPORTANTES POUR LA SÉRIE MS ONDULEUR/CHARGEUR QUI DOIVENT ETRE SUIVIES PENDANT L’INSTALLATION ET FONCTIONNEMENT DE CE PRODUIT. Avant d’utiliser la série MS, lire toutes les instructions etles mises en garde. Aussi, n’oubliez pas depasser en revue les différents manuels fournispour chaque composant du système. Lesinstructions d’installation sont pour une utilisationpar du personnel qualifié.
Safety Information • • Protection contre les surintensités pour le câblage de sortie AC n’est pas fourni en tant que partie intégrante de cet onduleur. Protection contre les surintensités du câblage de sortie CA doit être fournie dans le cadre de l’installation du système. Reportez-vous à la Section 2.5 Câblage ca dans le chapitre d’installation pour plus d’informations. Le conducteur de sortie CA conducteurs neutre et continue négative ne sont pas connectés (servitude) au châssis inverseur.
Table of Contents 1.0 Introduction ........................................................................................... 1 1.1 How an Inverter/Charger Works ....................................................................... 2 1.1.1 Inverter Applications for Permanent Installations .............................................. 2 1.1.2 Inverter Applications for Mobile Installations .................................................... 2 1.
Table of Contents (Cont.) 3.0 Operation ............................................................................................. 45 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 Inverter Mode ...............................................................................................45 Standby Mode ...............................................................................................47 Battery Charging ...........................................................................................
List of Figures Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure 1-1, Power Switch, Status LED, and Accessory Connection Ports ................................. 3 1-2, Electrical Connection Points ..................................
List of Figures (Cont.) Figure Figure Figure Figure Figure Figure Figure B-1, B-2, B-3, B-4, B-5, B-6, C-1, Series Battery Wiring ................................................................................... Parallel Battery Wiring ................................................................................. Series-Parallel Battery Wiring ....................................................................... Battery Bank Wiring Examples (12-volt) ................................................
Introduction 1.0 Introduction Congratulations on your purchase of a MS Series inverter/charger from Sensata Technologies. The MS Series is a “pure” sine wave inverter designed especially for rugged mobile applications, home backup power, and standalone applications. Powerful, yet simple to use, this inverter/charger will provide you with years of trouble-free performance you have come to expect from Sensata. Installation is easy.
Introduction 1.1 How an Inverter/Charger Works There are two modes of operation associated with this inverter/charger: Inverter Mode When the inverter is properly connected to batteries and turned on, the direct current (DC) from the batteries is transformed into a pure sine wave alternating current (AC). This AC is similar to the voltage provided by your utility and is used to power any electrical appliances (i.e., AC loads) connected to the inverter’s output.
Introduction 1.3 Features and Benefits The MS Series inverter/charger is designed to allow easy access to wiring, circuit breakers, and controls. Its die cast baseplate with one-piece aluminum cover ensures maximum durability with minimum weight, as well as a cooler, more efficient operation. Note: While not pictured, the MS2000 models have the same features as those listed in this section.
Introduction 7 DC Equipment Ground Terminal – this connection is used to tie the exposed chassis of the inverter to the DC grounding system. This terminal accepts CU/AL conductors from #14 to #2 AWG (2.1 to 33.6 mm2). Tightening torque is 45 in-lb. 8 AC Entry/Exit Connections – two 3/4” knockouts provided with cable-clamp strain reliefs to accommodate and secure the AC input and output field wiring.
Introduction The left side of MS Series inverters are equipped with the following features (Figures 1-3 & 1-4): 13 Exhaust Air Vents – ventilation openings that allow heated air to be removed by the internal cooling fan. 14 Model/Serial Number Label – includes model/serial number information, date of manufacture, and inverter and charger specifications. See the MS specifications in Appendix A for more information and a list of available models.
Introduction AC Access Cover AC Output Circuit Breakers (on -15B, -20B output breaker models only) 17 16 15 AC Input Circuit Breaker Note: The model shown is not a -15B or -20B model, therefore it does not show any AC output breakers. Models without output breakers (CB1 & CB2) use carriage bolts to fill the breaker openings.
Installation 2.0 Installation Info: Installations should be performed by qualified personnel, such as a licensed or certified electrician. It is the installer’s responsibility to determine which safety codes apply and to ensure that all applicable installation requirements are followed. Applicable installation codes vary depending on the specific location and application of the installation. CAUTION: Review the “Important Product Safety Information” on pages ii-v before any installation.
Installation Generator Power 120/240VAC Output Utility Power 120/240VAC Output ME-AGS-N Auto Gen Start Controller (Magnum Accessory) or r Generat Flux Capacito ME-RC50 AC Transfer Switch ME-ARC50 PWR FAULT CHG SELECT INV ON/OFF CHARGER ON/OFF INVERTER SHORE AGS METER SETUP TECH Remote Controls (Magnum Accessories) Main Panel OFF OFF OFF OFF OFF OFF ON ON ON ON OFF OFF OFF ON ON ON ON ON ON OFF ON ON ON ON ON ON OFF ON ON ON ON OFF OFF ON OFF ME-BMK Battery Mon
Installation Generator Power 120/240VAC Output Utility Power 120/240VAC Output ME-AGS-N Auto Gen Start Controller (Magnum Accessory) ME-RC50 AC Transfer Switch ME-ARC50 PWR FAU LT CH G SE LECT I NV ON/OF F C HA R GE R ON/ OF F IN V E R T E R S HOR E AGS ME T ER S ET U P T EC H Remote Controls (Magnum Accessories) Sub-Panel Main Panel MS2000 Series Inverter/ Charger ON St ack /Ac c ess or ies Net w ork Rem ote Bat tery T emp Sens or OF F P owe r ON /OF F Ch argi ng/Inv ert in g ON OFF
Installation 2.1.3 Locating the Inverter Only install the inverter in a location that meets the following requirements: Clean and Dry – The inverter should not be installed in an area that allows dust, fumes, insects, or rodents to enter or block the inverter’s ventilation openings. This area also must be free from any risk of condensation, water, or any other liquid that can enter or fall on the inverter.
Installation 2.2 Mounting the Inverter The inverter base can reach a temperature up to 90°C (194°F) and should be mounted on a noncombustible surface*. This surface and the mounting hardware must also be capable of supporting at least twice the weight of the inverter.
Left Side © 2016 Sensata Technologies 13 ¾" (34.9 cm) Mounting Holes Keyhole slots (x4) Use up to 9/32" (7 mm) screw/bolt Mounting Holes (x4) 8" (20.3 cm) Bottom 12" (30.5 cm) Front 12 ⅝" (32.1 cm) Top Air Intake Vents Air Intake Vents 4 ⅞" (12.4 cm) 2" (5.1 cm) 4 ⅞" (12.4 cm) 6 ⅝" (16.
Left Side Page 13 13 ¾" (34.9 cm) Mounting Holes Keyhole slots (x4) Use up to 9/32" (7 mm) screw/bolt Mounting Holes (x4) 6 ⅝" (16.8 cm) Bottom 12" (30.5 cm) Front 12 ⅝" (32.1 cm) Top Air Intake Vents Air Intake Vents 4 ⅞" (12.4 cm) 2" (5.1 cm) 4 ⅞" (12.4 cm) 6 ⅝" (16.
Installation 2.3 Wiring the Inverter – General Requirements This section describes the requirements and recommendations for wiring the MS Series inverter/ charger. Before wiring the MS Series inverter/charger, carefully read all instructions. Wiring should meet all local codes and standards and be performed by qualified personnel such as a licensed electrician.
Installation 2.4 DC Wiring This section describes the inverter’s required DC wire sizes, the recommended disconnect/ overcurrent protection, and how to make the DC connections to the inverter and the battery bank. Refer to Figure 2-6 when connecting the DC wires. WARNING: Even though DC voltage is “low voltage”, significant hazards may be present, particularly from short circuits of the battery system.
Installation MS Series Inverter/Charger (front view) BTS BTS Inverter’s DC Negative Busbar Inverter’s DC Positive Busbar Inverter’s Equipment Ground Wire Battery Temp Sensor Cable* MMP enclosure – for single inverter installations (includes DC disconnect breaker, DC shunt for battery monitor, and inverter DC busbars). If multiple inverters will be installed, see the MP enclosures - designed to allow up to four inverters to be connected together.
Installation 2.4.1 DC Wire Sizing It is important to use the correct sized DC wire to achieve maximum efficiency from the system and to reduce fire hazards associated with overheating. Always keep your wire runs as short as practical to prevent low voltage shutdowns and to keep the DC breaker from nuisance tripping (or open fuses) because of increased current draw. See Table 2-1 to select the minimum DC wire size (and corresponding overcurrent device) required based on your inverter model.
Installation If a fuse is used as an overcurrent device, a Class-T type or equivalent is recommended. This fuse type is rated for DC operation, can handle high short-circuit currents, and has a time delay that allows for momentary current surges from the inverter without opening the fuse. However, because the fuse can be energized from both directions, the NEC requires that it be installed in a manner that the power must be disconnected on both ends of the fuse before servicing.
Installation nut split washer CAUTION: Ensure nothing is placed between the cable ring lug and battery post. battery cable (with ring lug) battery post Figure 2-7, Battery Hardware Installation 2.4.4 CAUTION: Ensure nothing is placed between the DC terminal and ring lug.
Installation 2.4.5 Battery Temperature Sensor Installation and Wiring The Battery Temperature Sensor (shown in Figure 2-9) provides the inverter with precise battery temperature information to automatically adjust the ABSORB and FLOAT charge voltage set-points. This allows the batteries to be correctly charged under extreme temperature changes. If the temperature sensor is NOT installed and the batteries are subjected to large temperature changes, the battery life may be shortened.
Installation 2.4.6 Wiring the Inverter to the Battery Bank CAUTION: The inverter is NOT reverse polarity protected—if this happens the inverter will be damaged and will not be covered under warranty. Before connecting the DC wires from the batteries to the inverter, verify the correct battery voltage and polarity using a voltmeter. If the positive terminal of the battery is connected to the negative terminal of the inverter and vice versa, severe damage will result.
Installation 2.5 AC Wiring This section provides information on how to make the AC connections to the inverter using the correct AC wire size and corresponding overcurrent protection. See Figures 2-11 through 2-17. 2.5.1 Pre-AC Wiring Requirements CAUTION: Before installing any AC wiring, review the safety information at the beginning of this manual and the following to ensure a safe and long-lived system: • Always use properly rated circuit breakers.
Installation 2.5.3 Recommended GFCI (Ground Fault Circuit Interruption) Outlets In compliance with UL standards, Sensata tested the following series of GFCIs and found that they function properly when connected to the inverter’s AC output: • Hubbel #GF520EMBKA • • Leviton 8899-A, N7899, GFNT1, or GNNT2 Cooper VGF15W WARNING: Risk of electrical shock. Use only ground-fault circuit interrupters [receptacle(s) or circuit breaker(s)] compatible with your MS inverter/charger.
Installation 2.5.5 AC Conductor Wiring (MS2012, MS2812, MS2024, MS4024, & MS4048) The following steps are basic guidelines for installing and connecting the AC wiring to and from all MS Series inverters (except MS2000 Series model inverters—for instructions on wiring MS2000 Series model inverters, refer to Section 2.5.7). Before proceeding, refer to Table 2-3 to determine your AC wiring configurations.
Installation 2.5.6 AC Wiring Configurations (MS2012, MS2812, MS2024, MS4024, & MS4048) The following table provides the different wiring configurations for installing and connecting the AC conductors to and from the inverter (refer to Figures 2-11 to 2-15 for installation drawings showing these configurations). Refer to Table 2-4 (and Figures 2-16 & 2-17) for the MS2000 models.
Installation AC Terminal Block (AC input and output wiring) MS Series Inverter AC NEUT IN (from main panel) AC HOT 1 IN (from main panel) AC HOT 1 OUT (to sub-panel) AC NEUT OUT (to sub-panel) AC GROUNDS (to/from both panels) SINGLE IN / SINGLE OUT (30A) wiring In mobile installations: neutral is typically not connected to ground in main panel.
Installation AC Terminal Block (AC input and output wiring) MS Series Inverter AC NEUT IN (from main panel) AC HOT 1 IN (from main panel) AC HOT 2 IN (from main panel) AC HOT 1 OUT (to sub-panel) AC HOT 2 OUT (to sub-panel) AC NEUT OUT (to sub-panel) AC GROUNDS (to/from both panels) SINGLE IN / SINGLE OUT (60A) wiring In mobile installations: neutral is typically not connected to ground in main panel.
Installation AC Terminal Block (AC input and output wiring) MS Series Inverters MS2012-15B/-20B or MS4048-20B AC NEUT IN (from main panel) AC HOT 1 IN (from main panel) AC HOT 2 IN (from main panel) AC HOT 1 OUT AC HOT 2 OUT AC NEUT OUT (x2) AC GROUNDS (to/from both panels) SINGLE IN / DUAL OUT wiring In mobile installations: neutral is typically not connected to ground in main panel.
Installation AC Terminal Block (AC input and output wiring) MS Series Inverter AC NEUT IN (from main panel) AC HOT 1 IN (from main panel) AC HOT 2 IN (from main panel) AC HOT 2 OUT (to sub-panel) AC NEUT OUT (to sub-panel) AC GROUNDS (to/from both panels) DUAL IN / SINGLE OUT wiring In mobile installations: neutral is typically not connected to ground in main panel. ON ON OFF OF F ON OF F OF F ON ON OF F ON OF F OF F ON OF F ON OF F ON ON OF F ON ON OF F ON OF F 30 Maximum.
Installation AC Terminal Block (AC input and output wiring) MS Series Inverter AC NEUT IN (from main panel) AC HOT 1 IN (from main panel) AC HOT 2 IN (from main panel) AC HOT 1 OUT (to sub-panel) AC HOT 2 OUT (to sub-panel) AC NEUT OUT (to sub-panel) AC GROUNDS (to/from both panels) DUAL IN / DUAL OUT wiring In mobile installations: neutral is typically not connected to ground in main panel.
Installation 2.5.7 AC Conductor Wiring (MS2000 models) The MS2000 offers a cost-effective alternative to the MS2012 while still providing the same features. This model has a slightly smaller height, but otherwise has the same footprint as the other MS Series inverters. The MS2000 uses wire leads to connect the AC wires and can be wired in a single in – single out configuration, as well as a single in – dual out configuration (-15B & -20B).
Installation 2.5.8 AC Wiring Configuration (MS2000 models) The following table provides the different wiring configurations for installing and connecting the AC conductors to and from MS2000 model inverters (see Figures 2-16 and 2-17 for installation diagrams showing these configurations).
Installation AC Terminal Block (AC input and output wiring) MS2000 Inverter BLACK AC HOT IN WHITE AC NEUT IN GREEN AC GROUND AC GROUND .WHITE w./ BLACK AC. NEUT. OUT. AC HOT. 1 OUT BLUE SINGLE IN / SINGLE OUT (30A) wiring In mobile installations: neutral is typically not connected to ground in the main panel. ON ON OF F ON OF F ON ON OF F OF F ON ON OF F ON OF F ON ON OF F OF F OF F OF F ON ON OF F ON ON OF F ON ON OF F OF F 30 OF F OF F ..Maximum..
Installation AC Terminal Block (AC input and output wiring) BLACK Has optional 15-amp or 20amp branch-rated circuit breakers (on side of unit). AC HOT IN WHITE MS2000-15B/ MS2000-20B Inverters AC NEUT IN GREEN AC GROUND AC GROUND (x2) .WHITE w./ BLACK AC NEUT OUT .WHITE w./ BLACK AC NEUT OUT BLUE AC HOT. 1 OUT AC HOT. 2 OUT ORANGE SINGLE IN / DUAL OUT wiring In mobile installations: neutral is typically not connected to ground in the main panel.
Installation 2.6 Grounding Inverters The inverter/charger should always be connected to a permanent, grounded wiring system. An inverter system that is properly grounded will limit the risk of electrical shock, reduce radio frequency noise from the inverter, and minimize excessive surge voltages induced by lightning. This is done by ensuring there is a well-defined, very low-resistance path from the electrical system to the grounding system.
Installation 2.6.1 Sizing the Grounding Electrode Conductors AC Side – The size of the AC grounding electrode conductor (GEC – AC) depends on the size of the largest ungrounded conductor feeding the AC load center. One #8 AWG (8.4 mm2) copper conductor will serve as an AC grounding electrode conductor (GEC – AC) for AC power conductors smaller than and including #2 AWG (33.6 mm2) copper. See Table 2-5 for additional values.
Installation Method 2 (Figure 2-20): When the AC and DC service panels are near each other, then the AC grounding electrode conductor (GEC – AC) and DC grounding electrode conductor (GEC – DC) can be connected to a single grounding electrode. In this method—since there are multiple connections to the DC grounding electrode (GEC – DC)—the size of the DC grounding electrode conductor cannot be smaller than the largest conductor in the DC system (usually the battery-to-inverter cable).
Installation 2.6.2 System Bonding Jumper The MS Series inverter does not include an internal bond between the grounded conductor (AC neutral/DC negative) and the equipment grounding terminals. This bond [system bonding jumper (SBJ)] is usually done in the main distribution panel for each electrical system. CAUTION: There should be one and only one point in each electrical system (both AC and DC) where the grounded conductor is attached to the grounding electrode conductor.
Installation 2.6.4 Grounding on Boats When installing the MS Series inverter/charger on a boat, there are several considerations that must be followed when grounding to ensure a safe installation, prevent galvanic corrosion, and to adhere to ABYC (American Boat and Yacht Council) standards. Ensure a Safe Ground Connection When AC on the boat is being supplied by shorepower, the onboard neutral should be connected to safety ground on the dock1.
Installation 2.6.5 Neutral to Safety Ground Bonding The standards for safely wiring residential, commercial, RV/truck, and marine installations in the United States require the neutral and safety ground to be connected at the AC source; whether it is the utility feed in your home, an inverter, or a generator. This is to establish a specification that maximizes the possibility that a circuit breaker will activate if a hot wire-to-ground fault occurs.
Installation 2.6.6 Disabling the Neutral-to-Ground Connection All MS Series inverter/chargers have the automatic neutral-to-ground switching feature. In some installations/jurisdictions, this feature must be disabled by disconnecting the neutral-to-ground connection¹. If you are not sure whether you must disable this feature, check your local code requirements. The following steps will guide you in disabling the neutral-to-ground switching feature.
Installation 2.7 Inverter Notification Requirements When an inverter is installed in a building, facility or structure, the NEC (National Electrical Code) requires a label or plaque to be provided. This label/plaque is required to be easily visible and provide information that informs personnel on the location of all electrical system disconnects. This is to ensure all power to a building is quickly located and shut down in an emergency.
Installation 2.9 Functional Test After all electrical connections to the inverter, batteries, AC source and sub-panel have been completed, follow these steps to test the installation and the inverter’s operation. CAUTION: Use a multimeter to verify the correct DC voltage for your particular inverter model (i.e.
Installation AC Terminal Block AC Output 120 Vac (± 5%) 3 30 0 Neutral to Ground < 0.5 Vac Figure 2-27, AC Voltage Checks AC Wiring Compartment BLACK WHITE 08 09 10 Model: MS2000 Inverter/Charger Inverter Operation: Date Code 4 Year 06 07 Continuous output power: 2000 Watts @°C 25 Peak output current 29.0AAC, 10 sec surge (unregulated) Output provided with integral protection against overload DC Input: 10.0-15.5VDC Continuous input current: 225A @ 12.
Operation 3.0 Operation The MS Series inverter has two normal operating routines: Inverter mode, which powers your loads using the batteries, and Standby mode, which transfers the incoming AC current (i.e., utility power or a generator) to power your loads and to recharge the batteries. This inverter also includes an extensive protection circuitry to shut down the inverter under certain fault conditions. 3.1 Inverter Mode When the MS Series is first powered up, it defaults to the OFF mode.
Operation AC Hot Transfer Contact AC HOT 1 IN AC NEU IN AC HOT 1 OUT 120 VAC INPUT (30A) AC NEU OUT AC GROUND AC OUT Neutral-Ground Transfer Contact AC DC IN DC NEG DC DC POS FET Bridge Power Transformer Figure 3-2, Power Flow – Inverter Mode (MS2000 models) AC Hot Transfer Contact AC HOT 1 IN AC NEU IN CB2 Neutral-Ground Transfer Contact AC DC IN CB1 AC HOT 2 OUT INPUT (30A) AC GROUND AC HOT 1 OUT DC NEG DC DC POS FET Bridge 120 VAC AC NEU OUT AC OUT Power Transformer Figure
Operation 3.2 Standby Mode The MS Series features an internal battery charger and an automatic transfer relay when operating in Standby mode. Standby mode begins whenever AC power (utility or generator) is connected to the inverter’s AC input. Once the AC voltage and frequency of the incoming AC power is within the AC input limits, an automatic AC transfer relay is activated. This transfer relay passes the incoming AC power through the inverter to power the AC loads on the inverter’s output.
Operation AC IN AC Hot Transfer Contact AC HOT 1 IN 120 VAC AC NEU IN CB2 Neutral-Ground Transfer Contact AC DC IN CB1 AC HOT 2 OUT INPUT (30A) AC GROUND AC HOT 1 OUT DC NEG DC DC POS FET Bridge 120 VAC AC NEU OUT AC OUT Power Transformer Figure 3-6, Power Flow – Standby Mode (MS2000-15B/-20B models) 3.3 Battery Charging The MS Series is equipped with a PFC (Power Factor Corrected) and PI (Proportional-Integral) multi-stage battery charger.
Operation The Charge mode provides up to four separate charging stages: Bulk Charging, Absorb Charging, Float Charging and Full Charge (Figure 3-7). Bulk Charging: This is the initial stage of charging. While bulk charging, the charger supplies the battery with controlled constant current. The charger remains in bulk charge until the absorption charge voltage (determined by the Battery Type selection*) is achieved. The inverter’s green LED stays ON (solid) to indicate bulk charging.
Operation 3.4 Transfer Time While in Standby mode, the AC input is continually monitored. Whenever AC power falls below the VAC dropout voltage (80 VAC, default setting), the inverter automatically transfers back to Inverter mode with minimum interruption to your appliances—as long as the inverter is turned on. The transfer from Standby mode to Inverter mode occurs in approximately 16 milliseconds.
Operation 3.6 Protection Circuitry Operation The inverter is protected against fault conditions and in normal usage it will be rare to see any. However, if a condition occurs that is outside the inverter’s normal operating parameters, it will shut down and attempt to protect itself, the battery bank, and your AC loads. If there is a condition that causes the inverter to shut down, it may be one of the following conditions [also refer to the Troubleshooting section (Section 4.
Operation 3.7 Inverter Startup Power ON/OFF Switch – The inverter can be turned on and off by lightly pressing and releasing the Power ON/OFF switch on the front of the inverter (Figure 3-9). When the inverter is first connected to the batteries, or when its automatic protection circuit has turned the inverter off, the ON/OFF switch will need to be pressed to start the unit (or reset per Section 4.4).
Operation 3.8 Factory Default Values Your MS Series inverter/charger uses default values for the adjustable settings (Table 3-2) that are adequate for most installations. If some of your operating parameters need to be changed from the default values, an optional remote control can be used to make those changes. To help you determine if you need a remote display, information on the inverter/charger settings that can be changed is provided below.
Operation 3.9 Inverter Fan Operation The inverter contains two internal cooling fans that are automatically controlled. The speed of these fans is determined either by the internal temperature of the inverter or by the load on the inverter. The inverter’s fans will come on under the conditions listed below: • Fans run full speed if the internal transistors (FETS) or the power transformer reaches 80°C degrees Celsius (176°F), or the inverter is running at 100% of its rated load.
Maintenance and Troubleshooting 4.0 Maintenance and Troubleshooting The following information is provided to help you keep your MS Series inverter/charger in optimum operational condition. 4.1 Recommended Inverter and Battery Care The MS Series inverter/charger is designed to provide you with years of trouble-free service.
Maintenance and Troubleshooting 4.3 Troubleshooting The MS Series inverter/charger is a fairly simple device to troubleshoot. The following chart is designed to help you quickly pinpoint the most common inverter failures. Table 4-1, Basic Troubleshooting Symptom No output power. Inverter LED is OFF Possible Cause Recommended Solution Inverter is switched OFF Switch the inverter ON. Battery voltage is too low.
Maintenance and Troubleshooting 4.4 Resetting the Inverter Under some fault conditions (e.g., an internal fault), the inverter will need to be reset. Ensure all AC power (utility, generator, shorepower) is removed from the inverter’s input before resetting. CAUTION: If AC is connected while performing an inverter reset, damage may occur. 4.4.1 Performing an Inverter Reset To perform an inverter reset (also known as a “soft reset”): 1.
Appendix A – Specifications Appendix A – Specifications and Optional Equipment A-1 Inverter/Charger Specifications Models MS2000/12 MS2812 MS2012 (-15/-20B) MS2024 MS4024 MS4048 MS4048-20B Inverter Specifications Input battery voltage range 9.0 to 16.8 VDC Absolute maximum DC input 25 VDC 18.0 to 33.6 VDC 36.0 to 67.6 VDC 35 VDC AC output voltage accuracy 120 VAC ±5% (≤ continuous power) Output frequency and accuracy 60 Hz ± 0.
Appendix A – Specifications A-2 Inverter Efficiency The following curves are plotted to show the MS Series’ efficiency over the full power range and is displayed as a percentage. This graph represents the inverter’s efficiency while operating resistive loads. Motors and other inductive loads run less efficiently due to the impact of power factor losses.
Appendix A – Specifications A-4 Temperature and Inverter Output Continuous Inverter Power (kW) The following curves are plotted to show the MS Series inverters’ continuous output power at different ambient temperatures. 4.4 4.2 4.0 3.8 3.6 3.4 3.2 3.0 2.8 MS2812 MS4024 2.6 2.4 Note: Data for other models not available at this time. 2.2 2.0 1.
Appendix A – Specifications A-6 Optional Equipment and Accessories The following components are available for use with the MS Series inverter/charger. Some of these items are required depending upon the intended use of the inverter. MMP Series Enclosures The MMP175-30D, MMP175-60S, MMP250-30D, and MMP250-60S enclosures are for single inverter applications.
Appendix B – Battery Information Appendix B – Battery Information B-1 Battery Location Periodic maintenance (i.e., checking connections, cleaning, watering) on batteries is required. Locate the batteries in an accessible location to perform this maintenance. Batteries must be mounted in a clean, dry, ventilated environment where they are protected from high and low temperatures. The battery bank should be located as close to the inverter as possible without limiting access to the inverter’s disconnects.
Appendix B – Battery Information B-5 Battery Bank Sizing Worksheet Complete the steps below to determine the battery bank size required to power your AC loads: 1.
Appendix B – Battery Information B-6 Battery Wiring Configurations The battery bank must be wired to match the inverter’s DC input voltage. In addition, the batteries can be wired to provide additional run time. The various wiring configurations are: B-6.1 Series Wiring Wiring batteries in series increases the battery bank’s output voltage. A series connection combines each battery in a string until the total voltage matches the inverter’s DC requirement.
Appendix B – Battery Information overcurrent protection String (12 VDC @ 100 AH) to 12 VDC inverter (total capacity = 100 AH) 12 VDC battery (100 AH) 12-volt battery bank (one string of one 12-volt battery) overcurrent protection Series String (6 VDC + 6 VDC) 6 VDC battery (200 AH) to 12 VDC inverter (total capacity = 200 AH) 6 VDC battery (200 AH) 12-volt battery bank (one string of two 6-volt batteries wired in series) overcurrent protection Parallel String (100 AH + 100 AH) 12 VDC battery (1
Appendix B – Battery Information Series String (12 VDC + 12 VDC) 12 VDC battery (100 AH) 12 VDC battery (100 AH) overcurrent protection to 24 VDC inverter (total capacity = 100 AH) 24-volt battery bank (one string of two 12-volt batteries wired in series) overcurrent protection Series String (6 VDC + 6 VDC 6 VDC + 6 VDC + 6 VDC) battery (200 AH) 6 VDC battery (200 AH) 6 VDC battery (200 AH) 6 VDC battery (200 AH) to 24 VDC inverter (total capacity = 200 AH) 24-volt battery bank (one string of f
Appendix B – Battery Information overcurrent protection 6-volt battery (200 AH) 6-volt battery (200 AH) 6-volt battery (200 AH) 6-volt battery (200 AH) 6-volt battery (200 AH) 6-volt battery (200 AH) 6-volt battery (200 AH) 6-volt battery (200 AH) to 48 VDC inverter (total capacity = 200 Ahrs) 48-volt battery bank (one string of eight 6-volt batteries wired in series) overcurrent protection 12-volt battery (100 AH) 12-volt battery (100 AH) 12-volt battery (100 AH) 12-volt battery (100 AH) to
Appendix C – Power Consumption & Output Waveforms Appendix C – Power Consumption & Output Waveforms C-1 Appliances and Run Time The MS Series inverter/charger can power a wide range of household appliances including small motors, hair dryers, clocks, and other electrical devices. As with any appliance using batteries for power, there is a certain length of time that it can run—this is called “run time.
Appendix D – Inverter/Charger Terminology Appendix D – Inverter/Charger Terminology The following is a glossary of terms with which you may not be familiar. They appear in the various descriptions of inverter and battery charger operation. Absorption Stage – In this second stage of three stage charging, the batteries are held at a constant voltage (the absorb voltage setting) and the battery is charged to its maximum capacity. AC (Alternating Current) – Electrical current that varies with time (i.e.
Appendix D – Inverter/Charger Terminology Locked Rotor Amps – The current drawn by an electric motor with the shaft or rotor stopped and locked in position. This can be used to determine if an inverter has enough surge current to start a motor. If the inverter is capable of producing more amperage than the locked rotor amps rating of a motor, it will most likely start the motor easily. NEC (National Electric Code) – The guidelines and acceptable practices for electrical installations in the USA.
Appendix E – Warranty & Service Appendix E – Warranty & Service E-1 Limited Warranty Sensata Technologies warrants the MS Series to be free from defects in material and workmanship that result in product failure during normal usage, according to the following terms and conditions: 1. The limited warranty for the product extends for 36 months beginning from the product’s original date of purchase.
Magnum Energy Products Manufactured by: Sensata Technologies 2211 West Casino Rd. Everett, WA 98204 Phone: 425-353-8833 Fax: 425-353-8390 Web: www.SensataPower.