MagnaSine Hybrid – Mobile Series Pure Sine Wave Inverter/Charger MSH-Mobile Series Owner’s Manual TM
Disclaimer of Liability The use of this manual and the conditions or methods of installation, operation, use, and maintenance of the MSH-M Series inverter/charger is beyond the control of Magnum Energy, Inc. Therefore, this company does not assume responsibility and expressly disclaims liability for loss, damage, or expense whether direct, indirect, consequential or incidental that may arise out of or be any way connected with such installation, operation, use, or maintenance.
Safety Information IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS FOR THE MSH-M SERIES INVERTER/CHARGER THAT SHALL BE FOLLOWED DURING THE INSTALLATION AND OPERATION OF THIS PRODUCT. Before using the MSH-M Series, read all instructions and cautionary markings. Also, be sure to review the individual manuals provided for each component of the system. The installation instructions are for use by qualified personnel only.
Safety Information • • Overcurrent protection for the AC output wiring is not provided as an integral part of this inverter. Overcurrent protection of the AC output wiring must be provided as part of the system installation. Refer to Section 2.5 “AC Wiring” for more information. Note: An output breaker is provided on the inverter to provide overcurrent protection to the inverter’s internal wires; however, this output breaker is not rated to protect the AC output wiring.
Safety Information CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DE IMPORTANTES POUR LA SÉRIE MSH-M ONDULEUR/CHARGEUR QUI DOIVENT ETRE SUIVIES PENDANT L’INSTALLATION ET FONCTIONNEMENT DE CE PRODUIT. Avant d’utiliser la série MSH-M, lire toutes les instructions etles mises en garde. Aussi, n’oubliez pas depasser en revue les différents manuels fournispour chaque composant du système. Lesinstructions d’installation sont pour une utilisationpar du personnel qualifié.
Safety Information • partie intégrante de cet onduleur. Protection contre les surintensités du câblage de sortie CA doit être fournie dans le cadre de l’installation du système. Reportez-vous à la section Câblage ca dans le chapitre d’installation pour plus d’informations.
Table of Contents 1.0 Introduction ..................................................................................1 1.1 1.2 1.3 2.0 How the MSH-M Inverter/Charger Works ............................................................ 2 Advantages of using a Pure Sine Wave Inverter .................................................. 2 Features and Benefits ...................................................................................... 3 Installation .................................................
Table of Contents (Cont.) 3.5 3.6 3.7 3.8 3.9 3.10 3.10.1 4.0 Battery Temperature Sensor Operation .............................................................35 Protection Circuitry Operation ..........................................................................36 Inverter Startup ............................................................................................37 Factory Default Values ....................................................................................
List of Figures Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure 1-1, Power Switch, Status LED, and Accessory Connection Ports ................................ 3 1-2, Electrical Connection Points ...........................................................................
Introduction 1.0 Introduction Congratulations on your purchase of the MagnaSine Hybrid – Mobile (i.e., MSH-M) Series inverter/ charger from Magnum Energy. The MSH-M Series is a “hybrid” pure sine wave inverter designed especially for rugged mobile applications (i.e., trucks, RVs and boats). Powerful, yet simple to use, this inverter/charger will provide you with years of trouble-free performance you have come to expect from Magnum Energy.
Introduction 1.1 How the MSH-M Inverter/Charger Works There are two main modes of operation associated with the MSH-M inverter/charger: • Inverter Mode: When the inverter is properly connected to batteries and turned on, the direct current (DC) from the batteries is transformed into a pure sine wave alternating current (AC). This AC is similar to the voltage provided by your utility and is used to power any electrical appliances (i.e., AC loads) connected to the inverter’s output. • 1.
Introduction 1.3 Features and Benefits The MSH-M Series inverter/charger is designed to allow easy access to wiring, circuit breakers, and controls. Its die cast baseplate with one-piece aluminum cover ensures maximum durability with minimum weight, as well as cooler, more efficient operation. The front of the MSH-M inverter is equipped with the following features (refer to Figures 1-1 and 1-2): 1 Power ON/OFF Switch – a momentary pushbutton switch that alternately turns the inverter on or off.
Introduction 7 DC Equipment Ground Terminal – this connection is used to tie the exposed chassis of the inverter to the DC grounding system. This terminal accepts CU/AL conductors from #14 to #2 AWG (2.1 to 33.6 mm2). 8 AC Entry/Exit Connections – two 3/4” knockouts provided with cable-clamp strain reliefs to accommodate and secure the AC input and output field wiring. 9 Intake Air Vents – ventilation openings to pull in air to help keep the inverter cool for peak performance.
Introduction The left side of the MSH-M Series inverter is equipped with the following features (Figure 1-3): 13 Exhaust Air Vents – ventilation openings that allow heated air to be removed by the internal cooling fan. The exhaust air vents are located on the back side and at the rear on the right side; also see Figure 2-3 for the location of the air vents. 14 Model/Serial Number Label – includes model/serial number information, date of manufacture, and inverter and charger specifications.
Installation 2.0 Installation WARNING: Installations should be performed by qualified personnel, such as a licensed or certified electrician. It is the installer’s responsibility to determine which safety codes apply and to ensure that all applicable installation requirements are followed. Applicable installation codes vary depending on the specific location and application of the installation. CAUTION: Review the “Important Product Safety Information” on pages iii-vi before any installation.
Installation Generator Power 120VAC Output Shorepower 120VAC Output ME-AGS-N Auto Gen Start Controller (Magnum Accessory) tor or Genera Flux Capacit ME-ARC50 ME-RC50 AC Transfer Switch PWR FAULT CHG SELECT INV ON/OFF CHARGER ON/ OFF INVERTE R SHORE AGS METER SETUP TECH Remote Controls (Magnum Accessories) Main Panel OFF OFF OFF ON ON ON ON OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON OFF ON ON OFF ON ON OFF 30A ON OFF ON OFF ON OFF OFF ON OFF ME-BMK
Installation 2.1.3 Locating the Inverter Only install the inverter in a location that meets the following requirements: Clean and Dry – The inverter should not be installed in an area that allows dust, fumes, insects, or rodents to enter or block the inverter’s ventilation openings. This area also must be free from any risk of condensation, water, or any other liquid that can enter or fall on the inverter.
Installation 2.2 Mounting the Inverter The inverter base can reach a temperature up to 90°C (194°F) and should be mounted on a noncombustible surface*. This surface and the mounting hardware must also be capable of supporting at least twice the weight of the inverter.
© 2013 Magnum Energy, Inc. Page 10 Left Side 60 60 30 8" (20.3 cm) Bottom 12" (30.5 cm) Front Air Intake Vents Air Intake Vents 4 ⅞" (12.4 cm) 2" (5.1 cm) 4 ⅞" (12.4 cm) Exhaust Air Vents Exhaust Air Vents Figure 2-3, MSH-M Series Dimensions and Side References 13 ¾" (34.9 cm) 12 ⅝" (32.1 cm) Top 6 ⅝" (16.8 cm) "WARNING- Risk of electrical shock.
Installation 2.3 Wiring the Inverter – General Requirements This section describes the requirements and recommendations for wiring the MSH-M Series inverter/ charger. Before wiring the MSH-M Series inverter/charger, carefully read all instructions. Wiring should meet all local codes and standards and be performed by qualified personnel such as a licensed electrician.
Installation 2.4 DC Wiring This section describes the inverter’s required DC wire sizes, the recommended disconnect/ overcurrent protection, and how to make the DC connections to the inverter and the battery bank. Refer to Figure 2-4 when connecting the DC wires. WARNING: Even though DC voltage is “low voltage”, significant hazards may be present, particularly from short circuits of the battery system.
Installation MSH-M Series Inverter/Charger (bottom view) Inverter’s DC Positive Connection Inverter’s DC Negative Connection Inverter’s Equipment Ground Connection BTS Negative Busbar (optional) Battery Disconnect Switch (required) ON Inverter’s Equipment Ground Wire OFF Battery/Inverter Cable Fuse (required) Battery Temp Sensor Cable DC Shunt (optional) CLASS T FUSE Battery Bank’s Positive Cable Positive Busbar (optional) Battery Bank’s Negative Cable DC System Grounding point (vehicle chassis/ fr
Installation 2.4.1 DC Wire Sizing It is important to use the correct sized DC wire to achieve maximum efficiency from the system and to reduce fire hazards associated with overheating. Always keep your wire runs as short as practical to prevent low voltage shutdowns and to keep the DC breaker from nuisance tripping (or open fuses) because of increased current draw. See Table 2-1 to select the minimum DC wire size (and corresponding overcurrent device) required based on your inverter model.
Installation Table 2-2, DC Wire Size For Increased Distance Inverter Model Minimum Recommended DC Wire Size (one way)* 5 feet or less 5 to 10 feet 10 to 15 feet MSH3012M #4/0 AWG (107.2 mm2) #4/0 AWG (107.2 mm2) x2 not recommended MSH4024M #2/0 AWG (67.4 mm2) #4/0 AWG (107.2 mm2) #4/0 AWG (107.2 mm2) x2 * Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F) in free air. 2.4.
Installation 2.4.4 Wiring the DC Overcurrent Protection Device A fuse/disconnect or circuit breaker must be provided in the DC positive line between the battery and the inverter to protect the DC wiring system. Mount the fuse block (or circuit breaker assembly) as near as practical to the batteries. For maximum protection, install it within 18 inches (45 cm) of the battery. 1.
Installation 2.4.6 Battery Temperature Sensor Installation and Wiring The Battery Temperature Sensor (shown in Figure 2-7) provides the inverter with precise battery temperature information to automatically adjust the charge voltage set-points (Absorb, Float or Constant Voltage). This allows the batteries to be correctly charged under extreme temperature changes. If the temperature sensor is NOT installed and the batteries are subjected to large temperature changes, the battery life may be shortened.
Installation 2.4.7 Wiring the Inverter to the Battery Bank CAUTION: The inverter is NOT reverse polarity protected—if this happens the inverter will be damaged and will not be covered under warranty. Before connecting the DC wires from the batteries to the inverter, verify the correct battery voltage and polarity using a voltmeter. If the positive terminal of the battery is connected to the negative terminal of the inverter and vice versa, severe damage will result.
Installation 2.5 AC Wiring This section provides information on how to make the AC connections to the inverter using the correct AC wire size and corresponding overcurrent protection. 2.5.1 Pre-AC Wiring Requirements CAUTION: Before installing any AC wiring, review the safety information at the beginning of this manual and the following to ensure a safe and long-lived system: • Always use properly rated circuit breakers.
Installation 2.5.3 Recommended GFCI (Ground Fault Circuit Interruption) Outlets Some electrical safety codes require the use of GFCI’s. In compliance with UL standards, Magnum Energy has tested the following GFCI’s and find that they function properly when connected to the inverter’s AC output: • Shock SentryTM #XGF15V-SP • Leviton Smart Lock #8899-A • Hubbel #GF520EMBKA CAUTION: GFCIs shall be installed in a recreational vehicle’s wiring system to protect all branch circuits. 2.5.
Installation 2.5.5 AC Conductor Wiring The following steps are basic guidelines for installing and connecting AC wiring to and from an MSH-M Series inverter. WARNING: Before making any AC connections, make sure the inverter is disconnected from the battery and no AC power is connected to the inverter. Remove the two Phillips screws on the AC wiring access cover (Item 15, Figure 1-3) to access the internal AC terminal block (see Figure 2-8). Wiring the Inverter AC Input 1.
Installation AC Terminal Block (AC input and output wiring) MSH-M Series Inverter NEUTRAL IN (from main panel) HOT IN (from main panel) HOT OUT (to sub-panel) NEUTRAL OUT (to sub-panel) AC GROUND (to/from both panels) In mobile installations: neutral is typically not connected to ground in main panel. ON ON OFF ON OFF ON OFF OFF ON ON OFF ON OFF OFF ON OFF A maximum 60-amp single-pole breaker is required on the inverter’s AC input.
Installation 2.6 Grounding Inverters The MSH-M Series inverter/charger uses both AC and DC electrical systems, therefore each electrical system is required to be properly connected to a permanent, common “ground” reference. An inverter that is properly grounded limits the risk of electrical shock, reduces radio frequency noise, and minimizes excessive surge voltages induced by lightning.
Installation 2.6.1 Equipment Grounding Conductors The inverter case and all other noncurrent-carrying exposed metal surfaces in the entire electrical system—that may be accidentally energized—must be grounded. The equipment-grounding conductor must be sized to safely carry the maximum ground-fault current likely to be imposed on it from where a ground-fault may occur.
Installation 2.6.4 Grounding on Boats When installing the MSH-M Series inverter/charger on a boat, there are several considerations that must be followed when grounding to ensure a safe installation, prevent galvanic corrosion, and to adhere to ABYC (American Boat and Yacht Council) standards. Ensure a Safe Ground Connection When AC on the boat is being supplied by shorepower, the onboard neutral should be connected to safety ground on the dock.
Installation 2.6.5 Neutral to Safety Ground Bonding The standards for safely wiring RV, truck, and marine installations in the United States require the neutral and safety ground to be connected at the AC source; whether it is a shorepower feed, an inverter, or a generator. This is to establish a specification that maximizes the possibility that a circuit breaker will activate if a hotwire-to-ground fault occurs.
Installation 2.6.6 Connecting a Large DC Ground Wire Some marine installations require the DC ground wire to be the same size or one size smaller than the negative cable. Use the following steps to allow a larger ground wire to be connected. 1. Locate the DC ground terminal (Item 7, in Figure 1-2). 2. Locate and remove the AC access cover plate (Item 15, in Figure 1-3) on the side of the inverter. 3. Within the AC wiring area, locate the hex nut on the back side of the DC ground terminal.
Installation 2.9 Functional Test After all electrical connections to the inverter, batteries, AC source and sub-panel have been completed, follow these steps to test the installation and the inverter’s operation. CAUTION: Use a multimeter to verify the correct DC voltage for your particular inverter model (i.e.
Operation 3.0 Operation The MSH-M Series inverter has two normal operating routines: Inverter mode, which powers your loads using the batteries, and Standby mode, which transfers the incoming AC current (i.e., shorepower power or a generator) to power your loads and to recharge the batteries. This inverter also includes an extensive protection circuitry to shut down the inverter under certain fault conditions. 3.1 Inverter Mode When the MSH-M Series is first powered up, it defaults to the OFF mode.
Operation 3.2 Standby Mode The MSH-M Series features an internal battery charger and an automatic transfer relay when operating in Standby mode. The Standby mode begins whenever AC power (shorepower or generator) is connected to the inverter’s AC input. Once the AC voltage and frequency of the incoming AC power is within the AC input limits, the AC transfer relay activates. This transfer relay passes the incoming AC power through the inverter to power the AC loads on the inverter’s output.
Operation The Charge mode provides up to four separate charging stages: Bulk Charging, Absorb Charging, Float Charging and Full Charge. Bulk Charging: This is the initial stage of charging. While bulk charging, the charger supplies the battery with controlled constant current. The charger will remain in bulk charge until the absorption charge voltage (determined by the Battery Type selection*) is achieved. The inverter’s green LED stays ON (solid) to indicate bulk charging.
Operation 3.2.2 Load Support While in the Standby Mode and the charger is enabled, the MSH-M Series inverter/charger has the ability to work in parallel with the incoming AC source to support the AC loads using current from the batteries. During the Standby mode, the current and voltage from the AC source and the AC load current are continually monitored.
Operation 3.3 Current Flow The following figures show the current flow in the MSH-M Series during different modes: Inverting – The MSH inverter converts the current from the battery to power the AC loads. MSH Inverter DC Current (Battery) AC Current (Grid/Gen) 0A -10A AC Loads (Small) +10A Figure 3-4, MSH Current Flow – Inverting Charging and AC Pass-thru – The MSH inverter uses current from the grid/generator to power the AC loads, and also converts this current to charge the battery.
Operation Load Support AAC – If AC loads are added that are above the capability of the grid/generator, the MSH converts current from the battery and combines it with the current from the grid/ generator to power the additional AC loads. DC Current (Battery) MSH Inverter AC Current (Grid/Gen) -20A -10A AC Loads (Large) +30A Figure 3-7, MSH Current Flow – Load Support AAC Load Support VDC – If the battery is being charged externally (i.e.
Operation 3.5 Battery Temperature Sensor Operation The plug-in Battery Temperature Sensor (BTS) is used to determine the battery’s temperature. This information allows the multi-stage battery charger to automatically adjust the battery charge voltages for optimum charging performance and longer battery life.
Operation 3.6 Protection Circuitry Operation The inverter is protected against fault conditions and in normal usage it will be rare to see any. However, if a condition occurs that is outside the inverter’s normal operating parameters, it will shut down and attempt to protect itself, the battery bank, and your AC loads. If there is a condition that causes the inverter to shut down, it may be one of the following conditions [also refer to the Troubleshooting section (Section 4.
Operation 3.7 Inverter Startup ON/OFF Switch – The inverter can be turned on and off by lightly pressing and releasing the Power ON/OFF switch on the front of the inverter (refer to Figure 3-10). When the inverter is first connected to the batteries, or when its automatic protection circuit has turned the inverter off, the ON/OFF switch will need to be pressed to start the unit (or reset per Section 4.4).
Operation 3.8 Factory Default Values Your MSH-M Series inverter/charger uses default values for the adjustable settings (shown in Table 3-2) that are adequate for most installations. If some of your operating parameters need to be changed from the default values, an optional remote control/display can be used to make those changes. To help you determine if you need a remote display, information on the inverter/charger settings that can be changed is provided below.
Operation 3.9 Inverter Fan Operation The inverter contains two internal cooling fans that are automatically controlled. The speed of these fans is determined either by the internal temperature of the inverter or by the load on the inverter. The inverter’s fans will come on under the conditions listed below: • Fans run full speed if the internal transistors (FETS) or the power transformer reaches 80°C (176°F), or the inverter is running at 100% of its rated load.
Maintenance and Troubleshooting 4.0 Maintenance and Troubleshooting The following information is provided to help you keep your MSH-M Series inverter/charger in optimum operational condition. 4.1 Recommended Inverter and Battery Care The MSH-M Series inverter/charger is designed to provide you with years of trouble-free service.
Maintenance and Troubleshooting 4.3 Troubleshooting The MSH-M Series inverter/charger is a fairly simple device to troubleshoot. The following chart is designed to help you quickly pinpoint the most common inverter failures. Table 4-1, Basic Inverter Troubleshooting (Remote not available) Symptom Possible Cause N o o u t p u t p o w e r. Inverter is switched OFF. Inverter LED is OFF. Battery voltage is too low.
Maintenance and Troubleshooting 4.4 Performing an Inverter Reset To perform an inverter reset (also known as a “soft reset”): 1. First, ensure all AC power (i.e., shorepower or generator) is removed from the inverter’s input. 2. Press and hold the Power ON/OFF pushbutton (see Figure 4-1) for approximately ten (10) seconds until the Charging/Inverting Status LED comes on and flashes rapidly. 3. Once the rapid flashing has begun, release the Power ON/OFF pushbutton.
Appendix A – Specifications Appendix A – Specifications and Optional Equipment A-1 Inverter/Charger Specifications Model MSH3012M MSH4024M Input battery voltage range 9.0 to 17.0 VDC 18.0 to 34.0 VDC Absolute maximum DC input 25 VDC 35 VDC Inverter Specifications AC output voltage accuracy 120 VAC ±3% (≤ continuous power) Output frequency and accuracy 60 Hz ± 0.
Appendix A – Specifications A-2 Inverter Efficiency The following curves are plotted to show the MSH-M Series’ efficiency over the full power range and is displayed as a percentage. This graph represents the inverter’s efficiency while operating resistive loads. Motors and other inductive loads run less efficiently due to the impact of power factor losses.
Appendix A – Specifications 06+ 0 6HULHV &KDUJH &XUUHQW YV 7HPSHUDWXUH &KDUJHU &XUUHQW $PSV 06+ 0 06+ 0 7HPSHUDWXUH LQ 'HJUHHV &HOFLXV Figure A-3, MSH-M Series Charge Current vs Temperature A-3 Optional Equipment and Accessories The following Magnum Energy components are available for use with the MSH-M Series inverter/ charger. Some of these items are required depending upon the intended use of the inverter.
Appendix B – Battery Information Appendix B – Battery Information B-1 Battery Location Periodic maintenance (i.e., checking connections, cleaning, watering) on batteries is required. Locate the batteries in an accessible location to perform this maintenance. Batteries must be mounted in a clean, dry, ventilated environment where they are protected from high and low temperatures. The battery bank should be located as close to the inverter as possible without limiting access to the inverter’s disconnects.
Appendix B – Battery Information B-5 Battery Bank Sizing Worksheet Complete the steps below to determine the battery bank size required to power your AC loads: 1.
Appendix B – Battery Information B-6 Battery Wiring Configurations The battery bank must be wired to match the inverter’s DC input voltage. In addition, the batteries can be wired to provide additional run time. The various wiring configurations are: B-6.1 Series Wiring Wiring batteries in series increases the battery bank’s output voltage. A series connection combines each battery in a string until the total voltage matches the inverter’s DC requirement.
Appendix B – Battery Information overcurrent protection String (12 VDC @ 100 AH) to to12 12VDC VDC inverter inverter (total (totalcapacity capacity ==100 AH) 100 AH) 12 VDC battery (100 AH) 12-volt battery bank (one string of one 12-volt battery) overcurrent protection Series String (6 VDC + 6 VDC) 6 VDC battery (200 AH) to to12 12VDC VDC inverter inverter (total (totalcapacity capacity = =200 200AH) AH) 6 VDC battery (200 AH) 12-volt battery bank (one string of two 6-volt batteries wired in serie
Appendix B – Battery Information overcurrent protection Series String (12 VDC + 12 VDC) 12 VDC battery (100 AH) 12 VDC battery (100 AH) to 24 VDC inverter (total capacity = 100 AH) 24-volt battery 24-volt batterybank bank(one (onestring stringofoftwo two12-volt 12-voltbatteries batterieswired wiredininseries) series) Series String (6 VDC + 6 VDC + 6 VDC + 6 VDC) overcurrent protection 6 VDC battery (200 AH) 6 VDC battery (200 AH) 6 VDC battery (200 AH) 6 VDC battery (200 AH) to 24 VDC inverter (
Appendix C – Power Consumption and Output Waveforms Appendix C – Power Consumption and Output Waveforms C-1 Appliance Power Consumption The MSH-M Series inverter/charger can power a wide range of household appliances including small motors, hair dryers, clocks, and other electrical devices. As with any appliance using batteries for power, there is a certain length of time that it can run—this is called “run time.
Appendix D – Inverter/Charger Terminology Appendix D – Inverter/Charger Terminology The following is a glossary of terms with which you may not be familiar. They appear in the various descriptions of inverter and battery charger operation. Absorption Stage – In this second stage of three stage charging, the batteries are held at a constant voltage (the absorb voltage setting) and the battery is charged to its maximum capacity.
Appendix D – Inverter/Charger Terminology Line Tie – Term used when the inverter is connected to public power or the “grid” system. Load(s) – An electrical item that draws power (i.e., lights, radio, refrigerator, etc.,) to work. Locked Rotor Amps – The current drawn by an electric motor with the shaft or rotor stopped and locked in position. This can be used to determine if an inverter has enough surge current to start a motor.
Appendix E – Warranty & Service Information Appendix E – Warranty and Service Information E-1 Limited Warranty Magnum Energy, Inc., warrants the MSH-M Series to be free from defects in material and workmanship that result in product failure during normal usage, according to the following terms and conditions: 1. The limited warranty extends for 36 months from the product’s original date of purchase. 2.
Magnum Energy, Inc. 2211 West Casino Rd. Everett, WA 98204 Phone: 425-353-8833 Fax: 425-353-8390 Web: www.magnumenergy.