Operator`s manual

16
Oil Press: Displays engine oil pressure. The display registers oil pressure between 0-100 psi. Normal
operating pressure is between 35-80 psi.
Eng Temp: Displays the temperature of the engine’s coolant. If the coolant temperature exceeds the Maximum
Water Temperature of 230° F the engine will automatically shut down. Zero “0” will be displayed until a
minimum temperature of 100° F is reached.
Fuel Level: Displays the level of fuel in the tank by percentage (50% = 1/2 tank, 75% = 3/4 tank, etc.). If the
fuel level drops below a programmed low fuel point – usually at 15%, a low fuel warning and optional audio
alarm will be activated. If the fuel level drops below the programmed low fuel limit, usually at five percent,
the engine will automatically shut down.
Vbat: Displays the engine battery voltage. A normal reading is 13-14V on 12 volt systems and 24-26 on 24
volt systems (with the engine running).
Additional information may be viewed while the unit is in “MANUAL” or “AUTO” mode. By pressing the “Page Select”
button, the operator will select one of the following screens; “Running” screen, “Password” screen, or “History” screen.
In each of these page selections the operator may press the S” or “T” buttons on the “DIAGNOSTICS” keypad to
display additional information as follows:
“Running” screen:The operator may press the “S” or “T” buttons on the “DIAGNOSTICS” keypad to display
the “Alarm List” screen, “ECU Alarm List” screen, “Run Hours” screen, “ECU Values” screen, Engine display
screen and Generator display screen.
“Password” screen: The operator may press the “S” or “T” buttons on the “DIAGNOSTICS” keypad to
move the cursor (>) up or down a list of text.
“History” screen:The operator may press the “S” or “T” buttons on the “DIAGNOSTICS” keypad to move
the cursor (>) up or down a list of recent alarm or shut down codes. Pressing the “Enter” button at a particular
selection will allow the operator to scroll to the right in the LCD window to view the generator operating
parameters at the time of the alarm or shut down. The history of alarms or codes is saved in the digital
controller. The most recent alarm or code is the first to be listed, with the time/date of the alarm or code at
the bottom of the screen. The controller stores up to 118 codes. When full, the controller will automatically
remove the oldest file. These codes will not be lost when the “CONTROL ON/OFF” toggle switch is powered off.