4 POSITION VOLTAGE SELECTOR SWITCH (OPTIONAL)
The voltage selector switch is located on a panel attached to the generator behind the door located next to the fuel
tank filler. The selector switch is a four position switch that mechanically changes the connections between the
generator output leads and the connection lugs on the main control panel. Voltage ranges are selected by rotating
the handle on the switch to the desired voltage.
NEVER CHANGE THE VOLTAGE SELECTOR SWITCH WHILE THE ENGINE IS RUN-
NING! This will cause severe arcing and damage to the switch and generator windings.
The voltage selector switch is equipped with a locking mechanism. Once the proper voltage has been selected, push
the red latch on the inside of the phase switch handle up and insert a padlock through the handle. By locking the
handle in place you will prevent unauthorized personnel from changing the switch settings.
Note: (The following applies to units without a convenience outlet buck transformer:) When the voltage selector switch
is in position for 277/480V 3Ø, voltage at the two GFCI duplex convenience outlets is 139 Volts and the voltage at
the three twist-lock outlets is 139/240 Volts. When the voltage selector switch is in position for 120/208V 3Ø, voltage
at the two GFCI duplex convenience outlets is 120 Volts and the voltage at the three twist-lock outlets is 120/208
Volts. When the voltage selector switch is in position for 120/240 3Ø (DELTA), voltage at the two GFCI duplex
convenience outlets is 120 Volts and the THREE TWIST LOCK OUTLETS SHOULD NOT BE USED. When the
voltage selector switch is in position for 120/240V 1Ø, voltage at the two GFCI duplex convenience outlets is 120
Volts and the voltage at the three twist-lock outlets is 120/240 Volts.
Note: Super Start Option: When the voltage selector switch is in position for 277/480V 3Ø, voltage at the two GFCI
duplex convenience outlets is 120 Volts. When the voltage selector switch is in position for 120/208V 3Ø, voltage at
the two GFCI duplex convenience outlets is 120 Volts and the voltage at the three twist-lock outlets is 120/208 Volts.
When the voltage selector switch is in position for 120/240 3Ø (DELTA), voltage at the two GFCI duplex convenience
outlets is 120 Volts and the THREE TWIST LOCK OUTLETS SHOULD NOT BE USED. When the voltage selector
switch is in position for 120/240V 1Ø, voltage at the two GFCI duplex convenience outlets is 120 Volts and the voltage