User Manual

23
I N I T I
A
L V
A
C U U M H O L D
# # # # # M I C R O N
B E T W E E N 3 K & 9 K
C O N T I N UE?
F I N
A
L V
A
C U U M L E V E L
# # # # # M I C R O N
B E T W E E N 1 K & 9 K
C O N T I N UE?
V
A
C U U M R U N T I M E
# # M I N
B E T W E E N 1 & 9 9 M I N
C O N T I N UE?
H O S E S O V E R C H
A
R G E
A
M O U N T # . # # K G
B E T W E E N 0 & 2. 2 L B
C O N T I N UE?
D E F
A
U L T M I N I M U M L I N E
V O L T
A
G E # # # V
A
C
B E T W E E N 9 0 & 1 2 0 V
A
C
C O N T I N UE?
E L E V
A
T I O N F R O M S E
A
L E V E L # # # # # F T
B E T W E E N 0 & 3 0 K F E E T
C O N T I N UE?
O I L L I F E V
A
C U U M R I S E
L E V E L # # # M I C R O N
B E T W E E N 2 5 & 2 0 0
C O N T I N UE?
O I L D R
A
I N M
A
X L E V E L
# # # M L
B E T W E E N 5 0 & 2 0 0 M L
C O N T I N UE?
M I N I M U M V
A
C U U M L E
A
K
L E V E L # # I N H G
B E T W E E N 1 5 & 2 5
C O N T I N UE?
H I G H V O L T
A
G E F L U S H
C H G
A
M T1 . 6 L B
B E T W E E N 0. 1 & 2. 0 L B
C O N T I N UE?
This feature is not applicable to the base RHS980 and
RHS980 with High voltage oil flush. Enabling this
feature will compromise the functionality of the unit.
Press START key
This feature is not applicable to the base RHS980 and
RHS980 with High voltage oil flush. Enabling this
feature will compromise the functionality of the unit.
Press START key
This screen prompts for the length of time the vacuum
pump will run during each cycle. There is one initial
cycle to pull the system for an initial vacuum leak test,
then a second cycle to obtain the final micron level.
Enter a number of minutes between 1 and 99. The
value will be displayed as it is entered. Press START
key. (Default is 10 MIN)
A small overcharge of refrigerant is necessary to
compensate for refrigerant which will remain in the
hose after a charge procedure. Enter the number of
KG between 0 and 0.99 (0 and 2.2 LB). The value will
be displayed as it is entered. Press START key.
Change to value must be verified by service
manager by entering a password. (Default is 0.02
KG (0.04 LB))
This feature is not applicable to the base RHS980 and
RHS980 with High voltage oil flush. Enabling this
feature will compromise the Functionality of the unit.
Press START key.
Elevation from sea level used to adjust pressure
transducer calibration. Enter a number in feet from 0
to 30,000 feet. The elevation can be obtained by
calling your local airport. Press START key. (Default is
400 FT)
This feature is not applicable to the base RHS980 and
RHS980 with High voltage oil flush. Enabling this
feature will compromise the functionality of the unit.
Press START key.
This feature is not applicable to the base RHS980 and
RHS980 with High voltage oil flush. Enabling this
feature will compromise the functionality of the unit.
Press START key.
During vacuum leak test, this value is used to
determine a pass or fail.
The Default value is 1.6 lbs for the HIGH VOLTAGE
OIL FLUSH. WARNING, DO NOT REDUCE THIS
SETTING TO LESS THAN 1.6 LBS AS THE
FLUSHING PROCESS WILL NOT BE COMPLETED
PROPERLY AND RESIDUAL OIL MAY BE LEFT IN
LINES. Press START key.