Installation & Service Instructions This is a Wall Mounted Powered Flue Condensing Combination Boiler Gas Fired Central Heating Unit. The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency) Regulations 1993 No 3083” and is deemed to meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:Type test for purpose of Regulation 5 certified by: Notified Body 0051.
Natural Gas Building Regulations and the Benchmark Commissioning Checklist Main Combi 24 HE G.C.No 47 474 02 CONTENTS Section Legislation 4 1.0 Introduction 5 2.0 General Layout 6 3.0 Appliance Operation 7 4.0 Technical Data 8 5.0 Dimensions and Fixings 9 6.0 System Details 10 7.0 Site Requirements 13 8.0 Installation 19 9.0 Commissioning 24 10.0 Completion 26 11.0 Servicing the Boiler 27 12.0 Changing Components 29 13.0 Electrical 39 14.0 Short Parts List 40 15.
INSTALLER NOTIFICATION GUIDELINES Choose Building Regulations Notification Route Competent Person's Self Certification Scheme Building Control Install and Commission this appliance to manufacturer's instructions Contact your relevant Local Authority Building Control (LABC) who will arrange an inspection or contact a government approved inspector Complete the Benchmark Checklist If you notify via CORGI Scheme, CORGI will then notify the relevant Local Authority Building Control Scheme on member's beha
LEGISLATION IMPORTANT - Installation, Commissioning, Service & Repair This appliance must be installed in accordance with the manufacturer’s instructions and the regulations in force. Read the instructions fully before installing or using the appliance. In GB, this must be carried out by a competent person as stated in the Gas Safety (Installation & Use) Regulations.
1.0 INTRODUCTION 1.1 Description 1. The Main Combi 24 HE is a fully automatic gas fired wall mounted condensing combination boiler. It is room sealed and fan assisted, and will provide central heating and mains fed domestic hot water. Case Front Panel 2. The boiler is set to give a maximum output of 25.2 kW (condensing). 3. It is designed for use on Natural Gas (G20) and can be converted to use Propane. 4. The boiler is suitable for use only on fully pumped sealed heating systems.
1 20 19 18 17 2 2.0 GENERAL LAYOUT 2.1 Layout 1. Air Pressure Switch 2. Expansion Vessel 3. Burner Manifold 4. Automatic Air Vent 5. DHW Plate Heat Exchanger 6. Circulation Pump 7. Drain Off Point 8. Pressure Relief Valve 9. Optional Integral Timer Position 10. Central Heating System Pressure Gauge 11. Control PCB 12. Control Box 16 13. 3-Way Valve Assembly 15 14. Condensate Trap 15. Flame Sensing Electrode 16. Spark Electrode 17. Burner 18.
3.0 APPLIANCE OPERATION NOTE: All delay timers mentioned in 3.1 and 3.2 are overridden by domestic hot water demand. 1 Central Heating Circuit 3.1 Central Heating Mode (Fig. 4) 27 1. With a demand for heating, the pump circulates water through the primary circuit. At a predetermined flow rate the central heating flow switch operates, initiating the ignition sequence. 2 3 4 7 26 5 2.
4.0 Appliance Type Appliance Category C12 C32 CAT II 2H 3P Heat Input CH kW Electrical Protection NOx Class Min 24.8 10.6 Flue Terminal Dimensions Central Heating Primary Circuit Pressures 3 Condensate Drain Max IPX4D 1” BSP Diameter Projection 24 9.8 Heat Output CH (Condensing) Max Min kW 25.2 10.1 Heat Input DHW Max kW Outercase Dimensions Casing Height Overall Height Inc Flue Elbow Casing Width Casing Depth 24.
5.0 DIMENSIONS AND FIXINGS G E Dimensions A A 780mm B 345mm C 450mm D 116mm Ø Min. B 360° Orientation E 185mm F 190mm C D G 131mm Tube Ø 100mm Fig. 6 F Condensate Drain 68mm Gas Inlet Heating Flow 95mm Domestic Hot Water Outlet 65mm Heating Return Cold Water Inlet 65mm 65mm 65mm 265mm 165.7mm View from under the appliance Left Hand Side of Boiler 130mm Fig.
6.0 6.1 SYSTEM DETAILS Information 1. The Main Combi 24 HE Condensing Combination Boiler is a ‘Water Byelaws Scheme - Approved Product’. To comply with the Water Byelaws your attention is drawn to the following installation requirements and notes (IRN). a) IRN 001 - See text of entry for installation requirements and notes. b) IRN 302 - Byelaw 14. 2. Reference to the WRc publications, ‘Water fittings and materials directory’ and ‘Water supply byelaws guide’ give full details of byelaws and the IRNs. 6.
6.0 SYSTEM DETAILS 6.5 System Filling and Pressurising 1. A filling point connection on the central heating return pipework must be provided to facilitate initial filling and pressurising and also any subsequent water loss replacement/refilling. Stop Valve 2. There are connection points on the mains cold water inlet and central heating return isolating taps to which the optional filling loop kit (Part No. 248221) can be assembled. 3.
Other Tap Outlets SYSTEM DETAILS 6.8 Domestic Hot Water Circuit 1. All DHW circuits, connections, fittings, etc. should be fully in accordance with relevant standards and water supply regulations. Expansion Vessel Boiler 2. Your attention is drawn to: for GB: Guidance G17 to G24 and recommendation R17 to R24 of the Water Regulations Guide. for IE: the current edition of I.S. 813 “Domestic Gas Installations”. Check Valve Pressure Reducing Valve 6.0 To Hot Taps Stop Tap Fig. 10 3.
7.0 SITE REQUIREMENTS 7.1 Location 20mm/5mm Min 450mm 5mm Min see *NOTE: 1. The boiler may be fitted to any suitable wall with the flue passing through an outside wall or roof and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse. (The boiler may be fitted inside a cupboard - see Section 7.3).
7.0 7.3 SITE REQUIREMENTS Ventilation of Compartments 1. Where the appliance is installed in a cupboard or compartment, no air vents are required. 2. BS 5440: Part 2 refers to room sealed appliances installed in compartments. The appliance will run sufficiently cool without ventilation. 7.4 Gas Supply 1. The gas installation should be in accordance with the relevant standards. In GB this is BS 6891. In IE this is the current edition of I.S. 813 “Domestic Gas Installations”. 2.
7.0 SITE REQUIREMENTS 7.6 Condensate Drain Termination to an internal soil and vent pipe Boiler FAILURE TO INSTALL THE CONDENSATE DISCHARGE PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE BOILER The condensate discharge pipe MUST NOT RISE at any point along its length. There MUST be a fall of AT LEAST 2.5° (50mm per metre) along the entire run. 50mm per metre of pip e run 2.5° M inimu m fall 1. The condensate outlet terminates in a 1” BSP nut and seal for the connection of 21.
7.0 SITE REQUIREMENTS 7.7 Flue NOTE: Due to the nature of the boiler a plume of water vapour will be discharged from the flue. This should be taken into account when siting the flue terminal. 1. The following guidelines indicate the general requirements for siting balanced flue terminals. For GB recommendations are given in BS 5440 Pt 1. For IE recommendations are given in the current edition of I.S. 813 “Domestic Gas Installations”. 2.
7.0 SITE REQUIREMENTS 7.8 Flue Dimensions The standard horizontal flue kit allows for flue lengths between 100mm and 685mm from elbow to terminal (Fig. 16). The maximum permissible flue length is: 4 metres. 7.9 m 5m 68 m 0m 10 Flue Trim 1. The rubber flue trim supplied may be fitted to either the outside wall or on the inner wall of installation. Fig. 16 7.10 Terminal Guard (Fig. 17) 1.
B A 7.0 SITE REQUIREMENTS 7.11 Flue Options 1. The Main Combi 24 HE can be fitted with flue systems as illustrated. 2. The standard flue is suitable only for horizontal applications. 3. Maximum permissible equivalent flue lengths are:Horizontal Concentric 4 metres Vertical Concentric 4 metres Vertical Twin Pipe 12 metres Horizontal Flues 4. Any additional “in line” bends in the flue system must be taken into consideration. Their equivalent lengths are:Concentric Pipes: 45° bend 0.5 metres 93° bend 1.
8.0 8.1 INSTALLATION Initial Preparation The gas supply, gas type and pressure must be checked for suitability before connection (see Section 7.4). 1. After considering the site requirements (see Section 7.0) position the fixing template on the wall ensuring it is level both horizontally and vertically. 2. Mark the position of the two most suitable fixing slots for the wall plate and boiler lower fixing holes. It is preferable to use the horizontal fixing slots. For side flue exit, mark as shown (Fig.
Wall Plate 8.0 8.4 INSTALLATION Fitting The Boiler 1. Lift the boiler using the lower edges. Engage the slots at the top rear of the boiler on the wall plate hooks (Fig. 20). 2. Ensure that the boiler is level and sits against the wall. 3. Take the two steel washers and remaining screws. Using the previously drilled and plugged holes, secure the bottom of the boiler to the wall (Fig. 21). Fig. 20 4. Remove the elbows, valves and sealing washers from the packaging.
8.0 INSTALLATION 8.6 Condensate Drain (see section 7.6) 1. Connect the condensate drain using the 1” BSP nut and seal supplied. Ensure the discharge of condensate complies with any national or local regulations in force (see British Gas “Guidance Notes for the Installation of Domestic Gas Condensing Boilers”. m 5m 68 m 0m 10 2. The condensate outlet terminates in a 1” BSP nut and seal for the connection of 21.
Waste Y 8.0 INSTALLATION 8.7 Fitting the Flue (Cont) 5. Mark dimension ‘Y’ on the flue as shown (Fig. 26). Carefully cut the waste material from the flue, ensuring that the ducts are square and free from burrs. 6. The inner flue duct support bracket may be in the waste portion of the flue. In this case retrieve the bracket before discarding the waste. Flue Fig. 26 7. Take the inner flue support bracket (if not already fitted) and engage it over the flue duct.
8.0 INSTALLATION 8.8 Making The Electrical Connections To connect the mains input cable proceed as follows:- Fig. 30 1. Slacken the facia panel securing screws and lift the outercase panel so that its securing tabs are clear of the facia. Remove the panel. 2. Completely undo the screws securing the facia panel and hinge it down (Fig. 29). Control Box Cover 3. Remove the control box cover securing screws. Disengage the barbs on the control box from the cover. Remove the cover (Fig. 30). 4.
9.0 COMMISSIONING 9.1 Commissioning the Boiler 1. Reference should be made to BS 5449 Section 5 when commissioning the boiler. 2. Open the mains water supply to the boiler. 3. Open all hot water taps to purge the DHW system. 4. Ensure that the filling loop is connected and open, then open the heating flow and return valves on the boiler. 5. Open the screw on the automatic air vent (Fig. 35). 6. The system must be flushed in accordance with BS 7593 (see Section 6.
9.0 COMMISSIONING 9.2 Checking the Burner Pressure 1. Turn on the gas and electrical supplies to the boiler and ensure that all external controls are calling for heat. 2. Set the hot water and central heating temperature controls to maximum and the selector switch to the OFF position (Fig. 37). Selector Switch 3. Slacken the pressure test point sealing screw on the gas valve and connect a pressure gauge (Fig. 38). 4. Disconnect the sensing tube from the gas valve.
10.0 COMPLETION 10.1 Case Front Panel Completion 1. Hinge the facia panel upwards and engage the securing screws. Refit the case front panel and tighten the screws (Fig. 40). 2. Instruct the user in the operation of the boiler and system, explaining the operational sequence. 3. Carefully read and complete all sections of the Benchmark Commissioning Checklist at the rear of this publication that are relevant to the appliance and installation.
11.0 SERVICING THE BOILER Case Front Panel 11 .1 Annual Servicing 1. For reasons of safety and economy, it is recommended that the boiler is serviced annually. Servicing must be performed by a competent person. 2. After servicing, complete the relevant Service Interval Record section of the Benchmark Commissioning Checklist at the rear of this publication. 3. Ensure that the boiler is cool. 4. Ensure that both the gas and electrical supplies to the boiler are isolated. Fig. 41 5.
Baffle Tab 11.0 SERVICING THE BOILER Spring Clip 11.1 Annual Servicing (Cont) 10. Ease the front edge of the left hand baffle upwards, disengaging the spring clip. Disengage the tab on the baffle from the slot in the fan hood (Fig.44). 11. Undo the screws securing the fan hood assembly to the appliance back panel, and draw the fan and hood assembly forwards (Fig. 45). Fig. 44 12.
12.0 CHANGING COMPONENTS IMPORTANT: When changing components ensure that both the gas and electrical supplies to the boiler are isolated before any work is started. Pressure Switch See Section 11.1 “Annual Servicing” for removal of case panel, door etc. 12.1 Fig. 49 Sensing Tubes Fan (Figs. 50 & 51) + 1. Note the positions of the three wires on the fan motor and remove them. Remove the sensing tube from the fan spigot. b br Pressure Switch Wires 2.
12.0 CHANGING COMPONENTS 12.3 Heat Exchanger (Fig. 52) 1. Remove the fan as described in section 12.1. 2. Drain the primary circuit. Prise the pipe connecting clips off the joints in the flow and return pipes. Remove the heat exchanger return pipe. 3. Lift the heat exchanger to disconnect the flow pipe joint. Withdraw it from the appliance, taking care not to damage the rear insulation piece. Pipe Connecting Clips 4.
12.0 CHANGING COMPONENTS 12.5 Injectors (Fig. 54) 1. Remove the burner as described in Section 12.4. 2. Undo the screws securing the injector manifold to the inlet elbow and remove the manifold. Injector Injector Manifold Inlet Elbow Fig. 54 3. Unscrew and replace injectors as required and examine the sealing gasket, replacing as necessary. Reassemble in reverse order. 12.6 Gasket Electrodes (Fig. 54) 1. Remove the four screws securing the combustion box door and remove the door. 2.
12.0 CHANGING COMPONENTS 12.8 Modulator Wires Gas Valve (Fig. 56) 1. Undo the nut on the gas feed pipe at the tap rail under the boiler. Ignition Lead Gas Valve 2. Completely undo the securing screws and hinge the facia panel down. 3. Disconnect the wires from the valve modulator and the ignition lead from the spark generator. Disconnect the pressure sensing pipe from the valve. Undo the screw securing the spark generator electrical plug to the valve and disconnect the plug. 4.
12.0 CHANGING COMPONENTS 12.11 Pump - Head Only (Figs. 58 & 59) 1. Drain the primary circuit and remove the socket head screws securing the pump head to the body and draw the head away. 2. Undo the screw on the pump wiring cover and remove the cover. Using a suitable flat bladed screw driver press the cable securing levers downwards to release each wire after noting their position. 3. A standard Grundfos 15-60 replacement head can now be fitted. Connect the wiring to the new head.
12.0 CHANGING COMPONENTS 12.14 Pressure Gauge (Figs. 61 & 62) 1. Drain the primary circuit and undo the nut on the pressure gauge capillary. 2. Remove the timer cover and ease the timer wiring aside. Undo the screws securing the gauge retaining bracket. Fig. 61 3. Remove the bracket and gauge assembly. Depress the barbs on the side of the gauge and remove the retaining bracket. Pressure Gauge Capillary Gauge Retaining Bracket 4. Reassemble in reverse order. 12.15 Expansion Vessel (Fig. 63) 1.
12.0 CHANGING COMPONENTS 12.17 Pressure Relief Valve (Fig. 65) 1. Drain the primary circuit. 2. Disconnect the discharge pipe from the valve. Using a suitable hexagon key undo the grub screw sufficiently to release the valve. 3. Note the orientation of the valve, rotate it and withdraw it from the manifold. 4. Fit the new valve and ‘O’ ring seal and set to the previously noted orientation. Reassemble in reverse order. 12.18 P.C.B. (Fig. 67) ‘O’ ring seal 1.
12.0 CHANGING COMPONENTS Plate Heat Exchanger 12.20 Plate Heat Exchanger (Fig. 68) Fig. 68 1. Drain the primary circuit. 2. While supporting the heat exchanger undo the screws securing it to the brass manifolds. 3. Withdraw the heat exchanger upwards and to the left of the gas valve, taking care not to damage any wires or controls. Rubber Seal Seals 4. There are four rubber seals between the manifolds and heat exchanger which may need replacement. 5. Ease the seals out of the manifold.
12.0 CHANGING COMPONENTS 12.21 Diverter Valve Assembly (Cont) Central Heating Pressure Differential Valve Microswitch & Bracket CH Pressure Differential Valve (Fig. 71) 1. Remove the DHW pressure differential valve as described above. Sensing Pipe 2. From the brass diverter manifold undo the nut on the heating flow pipe. Remove the screw securing the diverter manifold to the appliance lower bracket. By-pass Pipe Diaphragm 3.
12.0 CHANGING COMPONENTS Secondary Heat Exchanger 12.23 Secondary Heat Exchanger (Fig. 73) 1. Drain the primary circuit Pipe Connecting Clip 2. Undo the four screws securing the right hand case panel. Remove the panel. Fan Spigot Outlet Pipe Clamp Outer Drum Boiler Return Pipe Heat Exchanger Return Pipe Elbow Fan Spigot Outlet Pipe 3. Prise the connecting clips from the heat exchanger return pipe and the boiler return pipe. Remove the pipes. 4. Slacken the screws on the fan spigot outlet pipe clamp.
13.0 ELECTRICAL 13.
14.0 SHORT PARTS LIST 140 Short Parts List 44 22 131 135 A 63 154 Key G.C. No. No. Description Manufacturers Part No. 22 Fan 5112627 23 Pressure Switch 5112999 32 Heat Exchanger 5112431 41 Burner 5112770 44 E66 402 Injector - 1.
15.0 FAULT FINDING Carry out initial fault finding checks 1. Check that gas, water and electrical supplies are available at the boiler. Electrical supply = 230V ~ 50 Hz. CH water system pressurised to 0.5 bar when the boiler is cold. The preferred minimum gas pressure is 19.5mbar (natural gas), or 36mbar (propane). 2. Carry out electrical system checks, i.e. Ground Continuity, Resistance to Ground, Short Circuit and Polarity with a suitable meter.
15.0 FAULT FINDING Domestic Hot Water - Follow operational sequence Turn selector to neon illuminated NO Replace diaphragm Go to section ‘A’ YES YES Is mains water filter and differential assembly clean? YES NO YES Turn thermostat to max. Open DHW tap fully. DHW flow switch operated NO DHW flow rate more than 2.5l/min.
15.0 FAULT FINDING Fault Finding Solutions Sections A to E A Is there 230V at: 1. Main terminals L and N 2. Main terminal fuse 3. B NO Check electrical supply YES Replace fuse NO Selector terminals a & b and a & 3. PCB - M1 connector terminals 9 & 10 Check wiring Replace selector NO neon illuminated Replace PCB Is there 230V at: 1. 2. Pump NO If pump jammed, release NO PCB - M1 connector terminals 8 & 15 Replace pump Replace PCB YES Change pump supply cable C NO 1.
15.0 FAULT FINDING E F Check and correct if necessary 1. Electrical and pressure tube connections 2. Blockage of pressure tubes 3. Restriction in flue 4. Venturi Gas at burner NO NO Replace air pressure switch Ensure gas is on and purged PCB - M4 connector is approx 230V AC, terminals 36 & 38 YES Replace gas valve NO neon illuminated YES Turn selector switch to ‘Reset’ position NO Replace PCB G 1. 2. Check the burner setting pressure of the gas valve (see Section 9.
15.0 FAULT FINDING I Ensure that mains input terminal L is Live (230V) and N is Neutral (0V) YES Check and correct if necessary 1. Flame sensing electrode and lead connections 2. Electrode position YES Flame current should be 1 µA approx. J Boiler overheat thermostat operated or faulty, i.e. continuity across thermostat terminals Replace PCB NO NO Replace flame sensing electrode Allow to cool. Continuity across thermostat terminals more than 1.
BENCHMARK No. 5 1 1 5 8 0 9 GAS BOILER COMMISSIONING CHECKLIST COLLECTIVE MARK BOILER SERIAL No. NOTIFICATION No.
SERVICE INTERVAL RECORD It is recommended that your heating system is serviced regularly and that you complete the appropriate Service Interval Record Below. Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls SERVICE 1 DATE SERVICE 2 DATE ENGINEER NAME COMPANY NAME TEL No.
Publication No. 5115809 - Iss. 4 (04/2006) General Enquiries (GB) Tel. 08706 060 780 Technical (GB) Tel. 08706 049 049 Service (GB) Tel. Fax. 08701 655 644 01926 410 006 Literature Request (GB) Tel. 08706 060 623 Technical (IE) Tel. 1850 560570 All descriptions and illustrations provided in this leaflet have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet.
User’s Guide and Important Warranty Information Combi 24 HE This is a Wall Mounted Powered Flue Condensing Combination Boiler Gas Fired Central Heating Unit. The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency) Regulations 1993 No 3083” and is deemed to meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:Type test for purpose of Regulation 5 certified by: Notified Body 0051.
Natural Gas Dear User Main Combi 24 HE G.C.No 47 474 02 Thank you for choosing a Main Combination boiler. The following instructions are simple basic steps that you can take to ensure years of trouble free heating and hot water for your home. Points to note 12 Months Free Warranty - register today To receive your 12 months free warranty please complete the form supplied with the boiler or simply call heateam, the service division of Baxi Potterton on 08706 000 653 or visit our web site on www.
Operating the Boiler The Central Heating and Hot Water you need will be available when the gas and electricity supplies to the boiler are turned on with the timer and other heating controls in your system set correctly. Other heating controls are items such as room thermostats, cylinder thermostats and thermostatic radiator valves. To give the most energy efficient performance these controls can switch your boiler on and off even when your timer is on.
Fault Indication A Off Fast Flashing (2 every second) On Burner On Flame Failure Power On 1. Your Main Combi 24 HE has three neon indicators. The upper two function as boiler on and fault indicators. 2. Depending on the nature of the fault the upper two neons will illuminate, go off or flash. 3. There are five possible combinations, each indicating one or more fault conditions. These are described below.
Temperature Control 1. Central Heating: The central heating hot water flow temperature can be adjusted between 30° C (± 5° C) minimum and 85° C (± 5° C) maximum. 2. Turn the control knob clockwise to increase the temperature (Fig. 6). 3. In normal winter usage we recommend that the central heating temperature be set at maximum. 4. Domestic Hot Water: The temperature of the domestic hot water can be adjusted by turning the control knob clockwise to increase up to a maximum of 65° C (Fig. 7). 5.
Central Heating System Pressure Pressure Gauge 1. The water pressure in the central heating system is indicated by the pressure gauge. 2 1 3 4 0 bar Fig. 8 Normal Pressure (when cold) 2 3 1 2. With the system cold and the boiler not operating the pressure should be between 0.5 and 1.0 bar. During operation the pressure should not exceed 2.5 bar, and will normally be between 1.0 and 2.0 (Figs. 8 & 9). 3. A pressure of 3 or greater indicates a fault.
Servicing and Repair of your Boiler heateam can service and repair your boiler if your installer is not able to. Our Baxi Potterton trained heating experts will quickly get your heating and hot water working again. If your boiler is out of its free 12 month period, heateam can provide a competitive fixed price repair rate including parts, labour and VAT. To find out more call heateam on 08701 655 644, open Monday to Friday 8am - 6pm, weekend 8.30am - 2pm. An appointment convenient for you can be arranged.
For your Safety This appliance must have been installed in accordance with the manufacturer’s instructions and the regulations in force. GB - Heating Industry definition meaning England, Scotland, Wales, Northern Ireland, Isle of Man and the Channel Isles Any modification that may interfere with the normal operation of the appliance without express written permission from the manufacturer or his agent could invalidate the appliance warranty.
20mm/5mm Min 450mm 5mm Min see *NOTE: 200mm Min 780mm 2 Burner On 3 1 Reset Flame Failure 4 0 Power On bar 200mm Min Fig. 13 450mm Min For Servicing Purposes 8mm Min In Operation Fig.
In the unlikely event you have a problem with your boiler please check the following. No Heating/Hot Water 1. Is the electricity supply to your boiler switched on and the selector switch set to Central Heating and Hot Water? If so the Green ‘Power On’ neon will be on. 2. Is a fault suggested by the neon indicators? User to check fault diagnosis Yes - Identify as described on Page 4. No - Continue below 3. Is the gas supply turned on? 4. Is the mains water supply turned on? Contact your installer 5.
Warning ! If you smell gas Turn off the gas supply at the meter and call your gas supplier immediately. It is possible to isolate the boiler and at the isolating valve (Fig. 15). In GB, Transco operate a 24 hour emergency service and the telephone number will be listed in your telephone directory. Faulty boiler If it is known or suspected that a fault exists on the boiler, it must not be used until the fault has been corrected by a competent person.
Publication No. 5115813 - Iss. 3 (05/2005) heateam heateam is the national customer service division of Baxi Potterton providing a free warranty service within 12 months of installation of your boiler. If your installer is unable to rectify your boiler fault, by contacting one of our friendly advisors we can arrange an engineer if required.