Installation Manual
18
Majestic • ECHEL36IN/STIN, ECHEL48IN/STIN, ECHEL60IN, ECHEL72IN Installation Manual • 2406-970 Rev. C • 1/17 
D. Floor Protection
NOTICE: Install appliance on hard metal or wood surfaces 
extending full width and depth. DO NOT install directly 
on carpeting, vinyl, tile or any combustible material other 
than wood.
WARNING! Risk of Fire! Maintain specifi ed air space 
clearances to appliance and vent pipe:
•  Insulation and other materials must be secured to prevent 
accidental contact.
•  The chase must be properly blocked to prevent blown 
insulation or other combustibles from entering and 
making contact with fi replace or chimney.
•  Failure to maintain airspace could cause overheating 
and fi re.
Figure 3.10 Floor Protection
C.  Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the 
gas appliance and/or its vent system. In cooler climates 
the vent should be enclosed inside the chase.
NOTICE:  Treatment of ceiling fi restops and wall shield 
fi restops and construction of the chase may vary with the 
type of building. These instructions are not substitutes 
for the requirements of local building codes. Therefore, 
you MUST check local building codes to determine the 
requirements to these steps.
Chases should be constructed in the manner of all out-
side walls of the home to prevent cold air drafting prob-
lems. The chase should not break the outside building 
envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase 
should be insulated. Vapor and air infi ltration  barriers 
should be installed in the chase as per regional codes for 
the rest of the home. Additionally, in regions where cold 
air infi ltration may be an issue, the inside surfaces may be 
sheetrocked and taped (or an equivalent method may be 
used) to achieve maximum air tightness. 
To further prevent drafts, the wall shield and ceiling fi re-
stops should be caulked with caulk with a minimum of 
300ºF continuous exposure rating to seal gaps. Gas line 
holes and other openings should be caulked with caulk 
with a minimum of 300ºF continuous exposure rating or 
stuffed with unfaced insulation. If the appliance is being 
installed on a cement surface, a layer of plywood may be 
placed underneath to prevent conducting cold up into the 
room.
Note: Figure 3.8 and Figure 3.9, and Figure 3.10 show the 
fi replace installed on the fl oor. However, this fi replace  can 
be elevated off the fl oor provided that the fi replace is properly 
supported by framing materials and the ceiling clearances are 
maintained. 










