D. Use of Elbows
Diagonal runs have both vertical and horizontal vent as-
pects when calculating the effects. Use the rise for the
vertical aspect and the run for the horizontal aspect. See
Figure 4.4.
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216
mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A
length of straight pipe is allowed between two 45º elbows.
See Figure 4.4.
Figure 4.5 shows the vertical and horizontal offsets for
DVP or SLP elbows.
Figure 4.4
HORIZONTAL
VERTICAL
RUN
RISE
EFFECTIVE
LENGTH
Y
X
X
X
DVP
Pipe
Effective Length Rise/Run
Inches Millimeters Inches Millimeters
DVP4 4 102 2-3/4 70
DVP6 6 152 4-1/4 108
DVP12 12 305 8-1/2 216
DVP24 24 610 17 432
DVP36 36 914 25-1/2 648
DVP48 48 1219 34 864
DVP6A 3 to 6 76 to 152
2-1/8-4-1/4 54-108
DVP12A 3 to 12 76 to 305
2-1/8-8-1/2 54-216
Vent Type
X
Inches Millimeters
DVP 16-1/4 413
Figure 4.5 Vertical and Horizontal Offset for DVP and SLP Elbows
Vent
Type
XY
Inches Millimeters Inches Millimeters
DVP 4-1/2 114 17 432