Installation Manual

24
Majestic • ECHEL36IN/STIN, ECHEL48IN/STIN, ECHEL60IN, ECHEL72IN Installation Manual • 2406-970 Rev. C • 1/17
Figure 4.9
Top Vent - Horizontal Termination Venting with 1 elbow
H
1
V
1
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling restops.
ALWAYS maintain speci ed clearances around venting and restop systems.
Install wall shield and ceiling restops as speci ed.
Failure to keep insulation or other material away from vent pipe could cause re.
WARNING
Note: Use DVP Series
components only.
ECHEL36IN, ECHEL48IN, ECHEL60IN
V
1
Minimum H
1
Maximum
2 ft. 610 mm 1.5 ft. 457 mm
3 ft. 914 mm 6 ft. 1.8 m
4 ft. 1.2 m 9 ft. 2.7 m
5 ft. 1.5 m 12 ft. 3.7 m
6 ft. 1.8 m 15 ft. 4.6 m
7 ft. 2.1 m 18 ft. 5.5 m
8 ft. 2.4 m 21 ft. 6.4 m
V
1
+ H
1
= 63 ft. (19.2 m) Maximum
H
1
= 40 ft. (12.2 m) Maximum
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance.
• The ECHEL36IN, ECHEL48IN and ECHEL60IN require a minimum of 24 inches of vertical venting before attaching any
elbow to the appliance.
• The ECHEL36STIN, ECHEL48STIN and ECHEL72IN require a minimum of 36 inches of vertical venting before attaching
any elbow to the appliance.
ECHEL72IN
V
1
Minimum H
1
Maximum
3 ft. 914 mm 1-1/2 ft. 457 mm
4 ft. 1.2 m 6 ft. 1.8 m
5 ft. 1.5 m 9 ft. 2.7 m
6 ft. 1.8 m 12 ft. 3.7 m
7 ft. 2.1 m 15 ft. 4.6 m
8 ft. 2.4 m 18 ft. 5.5 m
9 ft. 2.7 m 21 ft. 6.4 m
V
1
+ H
1
= 63 ft. (19.2 m) Maximum
H
1
= 40 ft. (12.2 m) Maximum
ECHEL36STIN, ECHEL48STIN
V
1
Minimum H
1
Maximum
3 ft. 914 mm 6 ft. 1.8 m
4 ft. 1.2 m 9 ft. 2.7 m
5 ft. 1.5 m 12 ft. 3.7 m
6 ft. 1.8 m 15 ft. 4.6 m
7 ft. 2.1 m 18 ft. 5.5 m
8 ft. 2.4 m 21 ft. 6.4 m
V
1
+ H
1
= 63 ft. (19.2 m) Maximum
H
1
= 40 ft. (12.2 m) Maximum