Installation Manual
32
Majestic • ECHEL36IN/STIN, ECHEL48IN/STIN, ECHEL60IN, ECHEL72IN Installation Manual • 2406-970 Rev. C • 1/17 
Figure 5.3  Installing Ceiling Firestop
Figure 5.4 Installing the Attic Shield
C.  Install the Ceiling Firestop
A ceiling fi restop  MUST be used between 
fl oors and attics.
•  DVP pipe only - Frame an opening 10 in. 
by 10 in. (254 mm by 254 mm) whenever 
the vent penetrates a ceiling/fl oor.  See 
Figure 5.3.
•  Frame the area with the same sized lumber 
as used in ceiling/fl oor joist.
• The ceiling fi restop may be installed above or 
below the ceiling joists when installed with an 
attic insulation shield. It must be under joists 
between fl oors that are not insulated. Refer 
to Figure 5.4.
•  Secure with two fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-
lation around the vent. Insulation must be kept 
back from the pipe to prevent overheating.
ATTIC ABOVE
A
PIPE
DVP
A
10 in. (254 mm)
A
INSTALL ATTIC INSULATION SHIELDS
BEFORE OR AFTER INSTALLATION OF VENT SYSTEM
CEILING FIRESTOP
INSTALLED BELOW CEILING
CEILING FIRESTOP
INSTALLED ABOVE CEILING
D.  Install Attic Insulation Shield
WARNING! Fire Risk. DO NOT allow loose 
materials or insulation to touch vent. Hearth 
& Home Technologies requires the use of an 
attic shield.
The International Fuel Gas Code requires an 
attic shield constructed of 26 gauge minimum 
steel that extends at least 2 in. (51 mm) above 
insulation.
•  Attic insulation shields must meet specifi ed 
clearances to combustible materials and be 
secured in place.
•  An attic insulation shield kit is available from 
Hearth & Home Technologies. Contact your 
dealer to order. Install attic insulation shield 
according to instructions included with kit.