Installation Manual
41
Majestic • ECHEL36IN/STIN, ECHEL48IN/STIN, ECHEL60IN, ECHEL72IN Installation Manual • 2406-970 Rev. C • 1/17 
Termination Cap
(1 of 3)
Storm
Collar
Caulk
Screws
Figure 7.14
Figure 7.14
Install Vertical Termination Cap
•  Attach the vertical termination cap by sliding the inner 
collar of the cap into the inner fl ue of the pipe section  
while placing the outer collar of the cap over the outer 
fl ue of the pipe section.
• Secure the cap by driving three self-tapping screws 
(supplied) through the pilot holes in the outer collar of 
the cap into the outer fl ue of the pipe. See Figure 7.14.
Important Notice: Heat shields may not be fi eld constructed.
F.  Horizontal Termination Requirements 
Heat Shield Requirements for Horizontal 
Termination
WARNING! Risk of Fire! To prevent overheating and fi re, 
heat shields must extend through the entire wall thick-
ness.
•  DO NOT remove the heat shields attached to the 
wall shield fi restop and the horizontal termination cap 
(shown in Figure 7.15).
• Heat shields must overlap 1-1/2 in. (38 mm) mini-
mum.
There are two sections of the heat shield. One section 
is factory-attached to the wall shield fi restop.  The  other 
section is factory-attached to the cap. See Figure 7.15.
If the wall thickness does not allow the required 1-1/2 in. 
(38 mm) heat shield overlap when installed, an extended 
heat shield must be used.
•  If the wall thickness is less than 4 in./102 mm, the heat 
shields on the cap and wall shield fi restop must be 
trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST 
be maintained.
•  Use an extended heat shield if the fi nished wall thickness 
is greater than 7-1/4 in. (184 mm).
•  The extended heat shield may need to be cut to length 
maintaining suffi cient length for a 1-1/2 in. (38 mm) 
overlap between heat shields.
•  Attach the extended heat shield to either of the existing 
heat shields using the screws supplied with the extended 
heat shield. Refer to vent components diagrams in the 
back of this manual.
•  Rest the small leg on the extended heat shield on top 
of the pipe section to properly space it from the pipe 
section.