Installation Manual
42
Majestic • ECHEL36IN/STIN, ECHEL48IN/STIN, ECHEL60IN, ECHEL72IN Installation Manual • 2406-970 Rev. C • 1/17 
Note: When using termination caps with factory-supplied 
heat shield attached, no additional wall shield fi restop is 
required on the exterior side of a combustible wall.
Install Horizontal Termination Cap
WARNING! Risk of Fire! The telescoping fl ue  section  of 
the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of fl ue  telescoping 
section is required.
Failure to maintain overlap could cause overheating 
and fi re.
•  Vent termination must not be recessed in the wall. Siding 
may be brought to the edge of the cap base. 
• Flash and seal as appropriate for siding material at 
outside edges of cap.
• When installing a horizontal termination cap, follow 
the cap location guidelines as prescribed by current 
ANSI Z223.1 and CAN/CGA-B149 installation codes 
and refer to Section 4 of this manual.
CAUTION! Risk of Burns! Local codes may require in-
stallation of a cap shield to prevent anything or anyone 
from touching the hot cap.
NOTICE:  For certain exposures which require superior 
resistance to wind-driven rain penetration, a fl ashing  kit 
and HRC caps are available. When penetrating a brick 
wall, a brick extension kit is available for framing the brick.
Figure 7.15 Venting Through the Wall
INTERIOR
HEAT SHIELD OR
EXTENDED
HEAT SHIELD
WALL SHIELD
FIRESTOP
HEAT SHIELD
1-1/2 IN. (38 MM) MIN.
OVERLAP
SHEATHING
SLIP SECTION
CAN BE EXTENDED
INNER VENT
OUTER VENT
EXTERIOR