Installation Manual
59
Majestic • ECHEL36IN/STIN, ECHEL48IN/STIN, ECHEL60IN, ECHEL72IN Installation Manual • 2406-970 Rev. C • 1/17 
Non-Combustible Mantels
Note: All measurements in inches.
Figure 10.14 Minimum Vertical and Maximum Horizontal 
  Dimensions of Non-Combustibles - Overlap Fit 
Finishing
MEASUREMENTS FROM TOP EDGE 
OF THE APPLIANCE OPENING
4
5
6
13-16
3
2
1
6
7
8
9
10
11
18
31
MAX.
MIN.
TO CEILING
Measurement from top edge of opening
to bottom of appliance = 24-1/2 IN.
3 FT. MAXIMUM
4-1/2 IN. 
MINIMUM
FIREPLACE OPENING
See Appliance Dimension Diagram-Dimension B
Figure 3.1 (ECHEL36IN, ECHEL48IN)
Figure 3.2 (ECHEL60IN, ECHEL72IN)
Figure 3.3 (ECHEL36STIN, ECHEL48STIN)
Figure 10.16  Mantel Leg or Wall Projections 
  (Acceptable on both sides of opening)
7 IN. 
MINIMUM
UNLIMITED
FIREPLACE OPENING
See Appliance Dimension Diagram-Dimension B
Figure 3.1 (ECHEL36IN, ECHEL48IN)
Figure 3.2 (ECHEL60IN, ECHEL72IN)
Figure 3.3 (ECHEL36STIN, ECHEL48STIN)
Note: Clearance from opening 
to perpendicular wall.
Note: Clearance from opening 
to perpendicular wall.
Mantel Legs Or Wall Projections Extending Past The Face Of The Fireplace (Combustible or Non-Combustible)
Figure 10.17  Mantel Leg or Wall Projections 
  (Acceptable on both sides of opening)
OVERLAP FIT
Figure 10.15 Minimum Vertical and Maximum Horizontal 
  Dimensions of Non-Combustibles - Inside Fit 
 Finishing
MEASUREMENTS FROM TOP EDGE 
OF THE APPLIANCE OPENING
4
5
6
14-16
9
10
18
31 MIN.
MAX.
TO CEILING
Measurement from top edge of opening
to bottom of appliance = 24-1/2 IN.
7
11
INSIDE FIT
Note: All measurements in inches.