Installation Manuel

Majestic Sovereign Series • SA36/SA42C • Installers Manual • 4010-262 • Rev E • 07/19/16
10
B. Clearances
WARNING! Risk of Fire!
You must comply with all minimum air space clearances
tocombustiblesasspeciedinFigure3.2.DO NOT pack
required air spaces with insulation or other materials.
Framing or nishing material used on the front of, or in
frontof,thereplacecloserthantheminimumslistedmust
be constructed entirely of non-combustible materials (i.e.,
steel studs, concrete board, etc.). Failure to comply may
causere.
Figure 3.2 Clearances to Combustible Materials
Minimum Clearances to Combustibles
WITHIN ENCLOSURE AREA
Fireplace to backwall 3/4 in. (19 mm)
Fireplace to sidewall 3/4 in. (19 mm)
Top standoffs to header 0 in. (0 mm)
Door opening to sidewall 12 in. (305 mm)
MANTEL
Mantel minimum height 12 in. (305 mm)
above opening
Maximum mantel depth 12 in. (305 mm)
(insulation)
0 in. to level
of standoffs
Attic
Insulation
Shield
(ceiling)
(roof)
(attic)
(ceiling)
Ceiling Firestop
Offset/Return (secured
with hanger straps)
Storm Collar
Roof Flashing
3/4 in. (19 mm) to back &
sides of appliance
(except at nailing flanges
where it is 1/2 in. [13 mm])
Must have 2 in. (51 mm)
minimum clearance
to header
0 in.
to floor
2 in. (51 mm) min.
Shaded areas
represent
2 in. (51 mm) min.
air space clearance
required around pipe
Combustible Object
48 in.
1219 mm
Adapter attached here
(not shown)