Installation Manuel

Majestic Sovereign Series • SA36/SA42C • Installers Manual • 4010-262 • Rev E • 07/19/16
12
Figure 3.5 Framing the Fireplace
B
C
A
2 in. (51 mm)
min. air space
clearance
from chimney.
Header MUST NOT be notched!
D
D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be
reduced as long as minimum clearances are met.
A B* C** D
in.
43 23 41 1/2 8
mm
1092 584 1054 203
in.
49 23 41 1/2 8
mm
1245 584 1054 203
** Adjust header height for a raised floor under fireplace.
Model #
SA36
SA42
* If interior of chase will be drywalled, add the thickness to
this measurement.
1/2 in.
(13 mm)
Fireplace must be set out
1/2 in. (13 mm) in front of
the face of the framing
material.
D. Frame the Fireplace
NOTICE: Hearth extension design must be determined
before installation of replace.
If the replace is placed on the oor the maximum height
of a nished raised hearth is 2 in. (51 mm), if you want
a higher raised hearth the replace must be placed on a
platform.
The replace will t a framed opening of:
SA36:
41-1/2 in. (1054 mm) tall and 43 in. (1092 mm) wide,
SA42: 41-1/2 in. (1054 mm) tall and 49 in. (1245 mm) wide.
WARNING! Risk of Fire! You must comply with all
minimum air space clearances to combustibles. DO NOT
pack required air spaces with insulation or other materi-
als.
WARNING! Risk of Fire! Comply with all minimum clear-
ancesspecied.
A minimum 3/4 in. (19 mm) air clearance must be
maintained at the back and 3/4 in. (19 mm) to the sides
ofthereplaceassembly.
Chimney sections at any level require a 2
in. (51 mm) minimum air space clearance
between the framing and chimney section.
Figure 3.5 shows a typical framing (using 2 x 4 lumber)
of the replace, assuming combustible materials are
used. All required clearances to combustibles around the
replace must be adhered to. See Figure 3.2. Any framing
across the top of the replace must be above the level of
the top standoffs.
CAUTION! Risk of Cuts/Abrasions. Wear protective gloves
and safety glasses during installation. Sheet metal edges
are sharp.
WARNING! Risk of Fire! Prevent contact with sagging,
loose insulation.
DO NOT install against vapor barriers or exposed
insulation.
Secure insulation and vapor barriers.
Provide minimum air space clearances at the sides and
backofthereplaceassembly.
E. Secure and Level the Fireplace
This replace may be placed on either a combustible or
noncombustible continuous at surface. Follow the in-
structions for framing in Section 3. Slide the replace into
position. Be sure to provide the minimum 3/4 in. air clear-
ance at the sides and 3/4 in. at the back of the replace.
The replace should be positioned so the face of the non-
combustible material on the replace will be ush with the
face of the drywall on the walls.
Level the replace and shim as necessary.
The
nished cavity depth must be no less than 23 in.
(584 mm) from the nished backwall to the outside of front
wall framing.