Installation Manuel

Majestic Sovereign Series • SA36/SA42C • Installers Manual • 4010-262 • Rev E • 07/19/16
14
CAUTION! Risk of Cuts/Abrasions. Wear protective
gloves and safety glasses during installation. Sheet metal
edges are sharp.
CAUTION! Risk of Fire or Asphyxiation! DO NOT draw
outsidecombustionairfromwall,oororceilingcavity,or
enclosed spaces such as an attic or garage.
DO NOT place outside air hood close to exhaust vents or
chimneys. Fumes or odor could be drawn into the room
throughthereplace.
Locate outside air inlet to prevent blockage from leaves,
snow/ice, or other debris. Blockages could cause
combustion air starvation.
Figure 3.8 Outside Air Inlet Locations
Outlet placed
higher than 3 ft
below the
termination cap
Attic space
Garage or
combustible
liquids storage
Outlet blocked by
snow, leaves, etc.
Clear area
outside
house or in
ventilated
crawl space
YES
NO
NO
NO
NO
Factory-built
fireplace
Use UL181 Class 1 or Class 0 rigid or flexible ducting.
Install with short run or mainly straight duct, except small
dip for cold air trap which will help prevent flow of cold air.
Secure flex duct with screws or wire ties.
Figure 3.9 Outside Air Installation
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)))
)
))
)
)
)
))))
)
))
))
)))
)
)
))
))
))
)
))
)
))
)))
))
)
)
)
)
))
)
)
)
)
)
)
)
)
)
)
)
)
3 ft min. from
top of uppermost
chimney section
to air inlet.
G. Outside Air Kit (optional)
If you install an outside air kit, Hearth & Home Technolo-
gies recommends you utilize the shortest duct run to opti-
mize the performance of the outside air kit. The outside air
inlet hood should be positioned in a manner that will not
allow snow, leaves, etc. to block the inlet. In some instal-
lations the air duct may need to be run vertically. In such
an installation, a 3 ft (914 mm) height difference must be
maintained from the top of the uppermost chimney section
to the outside air inlet hood.
Refer to Figures 3.8 and 3.9 when placing the outside air
inlet hood.
The outside air kit is installed on the left hand side of the
replace.
Cut a 4-1/2 in. (114 mm) hole in outside wall to
accommodate air piping.
Use 4 in. (102 mm) ex (not supplied) to directly connect
outside air to replace intake. Insulate the pipe to prevent
frost condensation.
Use the supplied outside air inlet hood.
Seal between the wall and the pipe with silicone to
prevent moisture penetration and air leaks.
Seal between the outside air inlet hood and the house
with silicone to prevent air inltration.