Installation Manuel

Majestic Sovereign Series • SA36/SA42C • Installers Manual • 4010-262 • Rev E • 07/19/16
34
Firebox
Repack
insulation
knockout
Combustible
materials
Maintain air clearance
to combustibles.
Gas line
Combustible materials
may be located at zero
clearance to gas line
beyond 4 in. (102 mm)
from fireplace side.
Gas line
1 1/2 in. (38 mm)
air space around
pipe
Refractory
Seal with
fireplace mortar
or non-combust-
ible sealant
4 in.
(102 mm)
Outer shell
of fireplace
Figure 8.1 Gas Line Installation
8
Fireplace Setup
A. Gas Log/Lighter Provision
WARNING! Fire and/or Asphyxiation Risk! Use with
solidwoodfuelordecorativegasapplianceonly.Gasre
generates fumes.
A certied gas log lighter or decorative gas log set can be
installed in this replace.
Vented Gas Logs
Unvented Gas Logs
CAUTION! If an unvented gas appliance is installed in
the replace, the gas appliance must only be operated
with the replace glass door fully open (if included).
Only unvented gas log sets which have been found to
comply with the standard for unvented room heaters,
ANSI Z211.11.2, are to be installed in this replace. If
an unvented gas appliance is installed it must incorpo-
rate an automatic shutoff device, and must be installed
in accordance with the National Fuel Gas Code Z223.1,
Latest edition.
WARNING! Do Not operate an unvented gas log set in this
replacewiththechimneyremoved.
B. Wood Burning Inserts
WARNING! Risk of Fire! Improper installation of wood in-
sertsmaycausereplaceorchimneysystemtooverheat.
If a wood burning insert is being installed in this replace,
Hearth & Home Technologies recommends full reline of
the chimney.
Cooling air openings at the top of the chimney must not
be obstructed in any manner.
Hearth & Home Technologies recommends securing the
reline at the top of the ue and using the cap certied for
use with this replace system.
Maximum input is 100,000 BTU/hr.
Decorative gas appliance must be certied to ANSI
Z21.60/CSA 2.26 “Standard for Decorative Gas
Appliances for Installation in Vented Fireplaces”.
Must be installed in accordance with the National Fuel
Gas Code, ANSI Z223.1 and Natural Gas Installation
Code, CAN/CGA-B149.1-M95 or the Propane
Installation Code, CAN/CGA-B149.2-M95.
A gas log set must incorporate a gas shutoff.
Gas Log set requires the damper to be locked fully open.
A listed automatic damper system with safety interlock
may be used in this replace with only compatible,
listed gas log sets. See damper system manufacturer’s
instructions.
Knockouts are provided on both sides of the replace
and in refractories for 1/2 in. (13 mm) iron pipe.
Seal refractory around pipe with replace mortar or a
non-combustible sealant.