Majorsine Power Inverter INSTALLATION & OPERATION MANUAL
MAJORSINE Inverter Manual / M101.4 Majorpower Corporation 7011 Industrial Drive Mebane, NC 27302 Tel: 919.563.6610 Fax: 919.563.6620 Revision History Product Manual # Date Release M101.1 March 2004 Issue 1 M101.2 January 2006 Issue 2 M101.3 August 2006 Issue 3 M101.4 March 2008 Issue 4 Copyright Notice ©2008, Majorpower Corporation. All rights reserved.
MAJORSINE Inverter Manual / M101.4 Notes: Model Number: Serial Number: Installation Date: This user’s manual contains important technical instructions to be followed by qualified personnel responsible for the installation, start-up and maintenance of this unit. It is recommended that this manual be read attentively to insure safe and reliable operation of this equipment.
MAJORSINE Inverter Manual / M101.4 Warranty Majorpower Corporation Warranty Summary for MAJORSINE A standard 2 year manufacturer warranty is in effect for the products in our MAJORSINE Power Inverter family. The standard warranty includes depot repair or replacement of any unit that fails during the first two years in operation due to a defect in materials or workmanship. Any unit returned to the factory under warranty will be repaired or replaced at the discretion of Majorpower.
MAJORSINE Inverter Manual / M101.4 Table of Contents 1. INTRODUCTION.............................................................. 7 1-1 GENERAL INFORMATION ...............................................................7 2. IMPORTANT SAFETY INSTRUCTIONS.................... 8 2-1 SAFETY STATEMENT ....................................................................8 2-2 ADDITIONAL SAFETY NOTES........................................................8 2-3 SYMBOLS ..............................................
MAJORSINE Inverter Manual / M101.4 7-2 SNMP EXPANSION CARD SLOT (WEB)......................................30 7-3 RS-232 COMMUNICATION PORT (GUI)......................................31 8. TECHNICAL SPECIFICATIONS................................. 32 MAJORSINE1000-24-2U ................................................................32 MAJORSINE1000-48-2U ................................................................33 MAJORSINE2000-48-2U ................................................................
MAJORSINE Inverter Manual / M101.4 1. INTRODUCTION 1-1 General Information Thank you for choosing MAJORPOWER as the power products supplier to your company. MAJORSINE Power Inverters are designed and built for full reliability at multiple locations and variety of applications. These intelligent, dependable inverters provide economical AC Power for all your network needs. Operators spanning global continents have deployed the MAJORSINE as the choice for high availability AC power support from a DC source.
MAJORSINE Inverter Manual / M101.4 2. IMPORTANT SAFETY INSTRUCTIONS 2-1 Safety Statement SAVE THESE INSTRUCTIONS - This manual contains important inverter instructions that should be followed during installation and maintenance of the MAJORSINE inverter unit. To reduce the risk of electric shock, install the inverter in a temperature and humidity controlled indoor environment, free of conductive contaminants. Ambient temperature should not exceed 50oC (122oF).
MAJORSINE Inverter Manual / M101.4 Reduced air flow: Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised. Mechanical loading: Mounting of the inverter in a rack should be level and balanced. Wiring: Adequate input power must be supplied to the inverter for proper use; correct wiring sizes must be respected. Grounding: Reliable grounding of rack-mounted equipment should be maintained.
MAJORSINE Inverter Manual / M101.4 3. PRODUCT OVERVIEW 3-1 System Features The MAJORSINE series inverter is a highly reliable DC-AC inverter system, designed with advanced power electronics and microprocessor technology offering the following features: Self-Diagnosis The MAJORSINE series inverter is equipped with a self diagnosis microprocessor, able to identify and show all failure messages on the LED/LCD display, with visual/audio alarm.
MAJORSINE Inverter Manual / M101.4 3-2 Block Diagram MAJORSINE Inverter Block Diagram AC BYPASS INPUT FILTER BYPASS RELAY DC to DC Converter DC to AC Inverter DC AC DC INPUT FILTER DC DC AC OUTPUT OUTPUT RELAY BREAKER MAJORSINE inverters feature IGBT (Insulated Gate Bipolar Transistor) technology, minimizing weight and dimension, while enhancing output short circuit reliability and overload capacity.
MAJORSINE Inverter Manual / M101.4 3-3 Front Panel MAJORPOWER.COM Tel: 514.369.4919 Fax: 514.369.4817 http://www.majorpower.com ON/OFF buttons: These are the two power buttons for turning on or turning off the inverter. Once the inverter is on, the “ON” button works as the On-Line <=> Off-Line mode switching button. INVERTER ON Indicates the INVERTER has been turned on and is working normally (output is available to support load equipment).
MAJORSINE Inverter Manual / M101.4 Ventilator The ventilator on the front panel provides inverter cooling. Do NOT obstruct this vent or the fan exhaust in the back of the unit! Circuit Breaker (DC Input Breaker) The DC circuit breaker will be tripped if there is a “short circuit” condition within the inverter. Reverse polarity protection (input) and overload protection are integrated within the internal circuitry and neither of these faults should trip the DC breaker.
MAJORSINE Inverter Manual / M101.4 AC Input Terminal Terminal for bypass VAC input voltage. AC Input Breaker Breaker for AC input DC Input Terminal Terminal for VDC input voltage. FLOATING input “+” and “-”connection. Dry Contact Terminal Dry contact terminal is connected to two Form C relays. One is for “DC abnormal” and the other one is for “FAULT”. When input DC voltage or fault occurs, the internal contact relay will open/close.
MAJORSINE Inverter Manual / M101.4 Grounding: Chassis to Earth Ground connection should be made per customer installation specifications or prevailing safety jurisdiction authority. The inverter external safety ground plane is not switched by operation in any mode. Typically - the chassis is mounted in a rack or a conductor to ground plane is installed. 4. INSTALLATION 4-1 Delivery Upon receipt of goods, check the condition of the package.
MAJORSINE Inverter Manual / M101.4 Use the following recommended cable sizes when connecting power to the inverter.
MAJORSINE Inverter Manual / M101.4 5. OPERATION 5-1 Connecting the Input Power Once the DC power has been connected, engage the DC breaker to operate the inverter. Turn ON the AC bypass supply. Typically a circuit breaker in the service panel. Verify operation start-up sequence of the inverter and make settings changes as needed for the application. (See 5.3 or 5.3a – Front Panel Operation) 5-2 Connecting the Loads Calculate the total power consumption (VA) of the load being attached to the output.
MAJORSINE Inverter Manual / M101.4 5-3 Front Panel Operation (Firmware Version 0.0 or 3.1) 1. Make sure that the complete installation has been carried out correctly. When the breaker is turned on or the utility input is available, the LCD of the inverter will display either following message: SYSTEM IS AT OFF-LINE MODE SYSTEM IS AT ON-LINE MODE 2. Press the “ON” button for a minimum of one full second (and Release within 10 seconds) to start the system power.
MAJORSINE Inverter Manual / M101.4 5-3a Front Panel Operation – Settings @ Start-Up The INVERTER will automatically initiate self-checks and start-up after 10 seconds. Press ON Button at least 1 full sec. SET F=60 V= 115 I/P F=60 V= 118 Press the ON key for entry into programming pages. Chang Setting? Yes(ON) No(OFF) O/P FREQ=60HZ SEL.(D) Sure(ON) O/P VOL=120V SEL.(D) Sure(ON) 10SEC Time Out. Press the OFF key to enter into the INVERTER main start-up procedure or wait 10 secs.
MAJORSINE Inverter Manual / M101.4 5-4 “DATA” button You can use the "DATA" button to select the following information which is displayed on the LCD screen: A) Output voltage: Shows present output voltage. OUTPUT VOLT. *** . V *** B) Inverter voltage: Shows present “inverter” voltage. INVERTER VOLT. *** . V *** C) Output frequency: Shows present output frequency. OUTPUT FREQ. *** . Hz *** D) Bypass AC voltage: Shows present input bypass AC voltage. BYPASS AC VOLT *** .
MAJORSINE Inverter Manual / M101.4 F) Input DC voltage: Shows the input DC voltage. INPUT DC VOLTAGE *** . V *** G) Output current: Shows present output current. OUTPUT CURRENT *** . A *** H) Output VA: Shows present output Volt-Amp OUTPUT VA *** VA *** I) Output power: Shows present output power (Watt) OUTPUT POWER *** W *** J) Temperature: Shows the temperature inside the INVERTER TEMPERATURE *** . º C *** K) Firmware Version: Shows the CPU firmware version FIRMWARE VERSION *** V .
MAJORSINE Inverter Manual / M101.
MAJORSINE Inverter Manual / M101.4 b) When the inverter is over temperature (may be caused by overload, high ambient temperature or fan failure), LCD shows. ** INVERTER ** OVER TEMPERATURE c) When the temperature inside the INVERTER is too high, LCD shows. ** AMBIENT ** OVER TEMPERATURE d) When the INVERTER output is in “short circuit” detection mode, LCD shows. ** INVERTER ** SHORT CIRCUIT e) When the INVERTER output is overloaded beyond rated capacity, LCD shows.
MAJORSINE Inverter Manual / M101.4 h) When the INVERTER voltage is “low”, LCD shows. ** INVERTER ** UNDER VOLTAGE C) Bypass AC status a) When the input bypass voltage is normal, LCD shows. ** BYPASS AC ** NORMAL b) When the input bypass voltage is normal and INVERTER output is in “bypass mode”, LCD shows INVERTER : STD BY BYPASS : ON c) When the input bypass voltage is “too low”, LCD shows. ** BYPASS AC ** UNDER VOLTAGE d) When the input bypass voltage is “too high”, LCD shows.
MAJORSINE Inverter Manual / M101.4 e) When the input bypass is “over” normal frequency range, LCD shows. ** BYPASS AC ** OUT OF FREQ. f) When the output is overloaded, LCD shows. ** BYPASS AC ** OVER LOAD D) Input DC status a) When the input DC voltage is normal. ** INPUT DC ** NORMAL b) When the input DC voltage is under threshold, the LCD shows. ** INPUT DC ** LOW VOLTAGE c) When the input DC voltage is over threshold, the LCD shows.
MAJORSINE Inverter Manual / M101.4 e) When the input DC voltage is over voltage, INVERTER will switch to bypass mode (if bypass AC is available) and LCD shows. DC OVER VOLT INVERTER OFF 5-6 Error message If the following messages appear on the LCD screen, contact Majorpower at once. ** INVERTER ** SOFTSTART FAIL EEPROM NOT AVAILABLE EEPROM checksum error 6. MAINTENANCE AND TROUBLESHOOTING 6-1 Maintenance Make sure that the inverter vents are not blocked.
MAJORSINE Inverter Manual / M101.4 6-2 Troubleshooting Problem LEDs do not light up Possible cause Action to take The circuit breaker is “off” Turn on or reset the circuit breaker. DC cable polarity installation Apply correct DC polarity. DC input is “over” or “under” voltage. Apply correct DC voltage. Bypass AC fail AC voltage or frequency may be out of range. Inverter failure. Call for service. Output was “short”.
MAJORSINE Inverter Manual / M101.4 6-3 Alarms Inverter Alarm Classifications Fault Alarm Indicator includes: Bypass AC Input High or Low Voltage Bypass AC Input Frequency Out of Range Fan Fail Inverter Internal Failure Output Load Sensing “short” condition High Temperature Overload Indicator includes: The AC power drawn from the inverter exceeded the load rating of the inverter. See Section 8.
MAJORSINE Inverter Manual / M101.4 Bypass Utility AC Alarm Thresholds For 100VAC system AC Bypass Voltage Range AC Bypass Frequency Range F=50Hz AC Bypass Frequency Range F=60Hz AC Bypass Recovery From Over Voltage AC Bypass Recovery From Under Voltage O/P = 100Vac O/P = 110Vac O/P = 115Vac O/P = 120Vac 80Vac ~ 90Vac 95Vac ~ 100Vac 120Vac ~130Vac 135Vac ~140Vac 45.5Hz ~ 54.5Hz 55.5Hz ~ 64.
MAJORSINE Inverter Manual / M101.4 7. COMMUNICATION 7-1 Dry Contact Communication Terminal The “Dry Contact” terminal is the interface for two Form C relays. The relays are used for switching the voltage provided by the user’s external alarm system. One contact set is for “DC Abnormal” and the other one is for “FAULT”. When alarms in each classification trigger, the relay switches state. (Ref: Sec.
MAJORSINE Inverter Manual / M101.4 7-3 RS-232 Communication Port (GUI) The RS-232 communication port provides the following features using a GUI software package that is available by request from Majorpower Corporation: 1) Communicates Fault, DC abnormal, Overload, Inverter Fail etc. 2) Monitor and display output voltage, output load, input dc voltage and temperature. 3) Coupled with PC software application port, provides scheduled on/off function for inverter.
MAJORSINE Inverter Manual / M101.4 8. TECHNICAL SPECIFICATIONS MAJORSINE1000-24-2U DC Input Voltage Rated Current Protection Efficiency 20-30 VDC 50 Amps Fuse and DC Breaker >85% (full linear load), 24 VDC I/P, 120 VAC O/P AC Output Capacity Voltage Voltage Regulation Frequency Wave Form THD (linear load) THD (SPS load) Crest Factor Receptacles 1KVA / 800W 100, 110, 115, 120 VAC ±2% 50/60Hz ± 0.
MAJORSINE Inverter Manual / M101.4 MAJORSINE1000-48-2U DC Input Voltage Rated Current Protection Efficiency 40-60 VDC 25 Amps Fuse and DC Breaker >85% (full linear load), 48 VDC I/P, 120 VAC O/P AC Output Capacity Voltage Voltage Regulation Frequency Wave Form THD (linear load) THD (SPS load) Crest Factor Receptacles 1KVA / 800W 100, 110, 115, 120 VAC ±2% 50/60Hz ± 0.
MAJORSINE Inverter Manual / M101.4 MAJORSINE2000-48-2U DC Input Voltage Rated Current Protection Efficiency 40-60 VDC 50 Amps Fuse and DC Breaker >85% (full linear load), 48 VDC I/P, 120 VAC O/P AC Output Capacity Voltage Voltage Regulation Frequency Wave Form THD (linear load) THD (SPS load) Crest Factor Receptacles 2KVA / 1600W 100, 110, 115, 120 VAC ±2% 50/60Hz ± 0.
MAJORSINE Inverter Manual / M101.4 MAJORSINE1000-125-2U DC Input Voltage Rated Current Protection Efficiency 100-150 VDC 10 Amps Fuse and DC Breaker >85% (full linear load), 125 VDC I/P, 120 VAC O/P AC Output Capacity Voltage Voltage Regulation Frequency Wave Form THD (linear load) THD (SPS load) Crest Factor Receptacles 1KVA / 800W 100, 110, 115, 120 VAC ±2% 50/60Hz ± 0.
MAJORSINE Inverter Manual / M101.4 MAJORSINE2000-125-2U DC Input Voltage Rated Current Protection Efficiency 100-150 VDC 20 Amps Fuse and DC Breaker >85% (full linear load), 125 VDC I/P, 120 VAC O/P AC Output Capacity Voltage Voltage Regulation Frequency Wave Form THD (linear load) THD (SPS load) Crest Factor Receptacles 2KVA / 1600W 100, 110, 115, 120 VAC ±2% 50/60Hz ± 0.
MAJORSINE Inverter Manual / M101.4 MAJORSINE1000i-48-2U DC Input Voltage Rated Current Protection Efficiency 40-60 VDC 25 Amps Fuse and DC Breaker >85% (full linear load), 48 VDC I/P, 230 VAC O/P AC Output Capacity Voltage Voltage Regulation Frequency Wave Form THD (linear load) THD (SPS load) Crest Factor Receptacles 1KVA / 800W 208, 220, 230, 240 VAC ±2% 50/60Hz ± 0.
MAJORSINE Inverter Manual / M101.4 MAJORSINE2000i-48-2U DC Input Voltage Rated Current Protection Efficiency 40-60 VDC 50 Amps Fuse and DC Breaker >85% (full linear load), 48 VDC I/P, 230 VAC O/P AC Output Capacity Voltage Voltage Regulation Frequency Wave Form THD (linear load) THD (SPS load) Crest Factor Receptacles 2KVA / 1600W 208, 220, 230, 240 VAC ±2% 50/60Hz ± 0.
MAJORSINE Inverter Manual / M101.4 Drawing No.
MAJORSINE Inverter Manual / M101.4 9. Optional Hardware: SNMP Remote Communication Card: Remote monitoring is a prime consideration and requirement to manage multiple network elements from a central location. Remote access is established by simply installing the plug-n-play card, configuring your network IP address, and attaching the network interface cable. Locking - Hardwire Adapter: Reliable locking NEMA 5-15 plug to secure load circuits to the output sockets of the inverter.