Specifications

3. A non-combustible hearth extension
(floor protector) must be installed
under the unit. This extension must
be a minimum of 3/8 inch thick non-
combustable material such as brick,
concrete, slate, ceramic tile, or a
listed floor protection board such as
Wonderboard or Homosote. Check
with local building authorities as to
what other materials are acceptable.
The hearth extension must extend a
minimum of 5 1/2 inches beyond the
back and sides of the unit and 16
inches beyond the front opening of
the unit. Mark location of required
hearth extension on the floor. Refer
to Illustration No. 8.
4. Remove unit and install hearth ex-
tension.
5. Position unit on hearth extension at
the proper clearances with the flue
outlet directly below chimney.
Rotate unit as needed to make cer-
tain front opening is positioned par-
allel to the back wall for a side wall/
back wall installation, or at a 45 degree angle to both walls for a corner installation.
6. Chimney connector installation depends on the brand of chimney system installed. If using
Simpson Dura-Vent a Universal Connector part No. 1870 must be used. With Metalbestos either
the DSA or DSAC single wall chimney connector part must be used. Security users require the
UP adapter. With most chimney systems manufactured a similar part is available from the chimney
system manufacturer. If necessary contact the chimney manufacturer for proper connection parts
for your chimney system. Refer to Illustration No. 8.
Page - 8
Fire Drum 2
Continued
5 1/2"
5 1/2"
5 1/2"
Illustration No. 8
16"