SECTION 2 - Meter Configuration
Note: Disconnect the pulse input terminal block.
Reset Meter: Click the Reset Meter button to reset all data fields to zero.
Units: Enter units of measure. Example: KWH, GPM, LPM, CFM, BTUH, MWH, etc.
Maximum 5 alpha and/or numeric characters (uppercase and/or lowercase).
2.5.0
2.5.1
2.5.2
2.5.3
2.5.4
© Copyright 2009DN IS-IPSM101.1
® Registered trademark MAMAC SYSTEMS, Inc.
11 of 17
Caution: Before starting the IP Sub Metering Appliance, please insure that the time and date
are configured to maintain data integrity.
Constant: Input the meter constant. The meter constant is the value per pulse. For
example, if each pulse is equal to 100 Watts and the unit of measure is KWH, the meter
constant will be 0.100. Similarly, if the water meter gives a pulse each gallon of flow per
minute and the units are GPM, the meter constant will be 1.000. Meter constant can be from
0.001 to a maximum of 9.999.
12:57:39
May 1, 2009
IP Sub Metering Appliance:
Main
Data Logging
Configuration
UNO Meter
Configuration | Meter
Copyright 2009
c
www.mamacsys.com
R
Registered trademark MAMAC Systems, Inc.
METER CONFIGURATION
Constant:
1.000
Units:
KWH
Reset Meter
Save
Save: Click to save.
2.5.5
Note: Re-connect the pulse input terminal block. The IP Sub Metering Appliance is now
ready to log data.