Owner's Manual

20 Part Number: 000013325 Rev 02 6/17
Installation Section 2
,
Caution
The refrigeration system warranty will not apply if the
Manitowoc Ice Machine and Manitowoc ICVD Condensing
Unit are not installed according to specifications. This
warranty also will not apply if the refrigeration system is
modified with a condenser, heat reclaim device, or other
parts or assemblies not manufactured by Manitowoc.
Step 1 Secure the Condenser.
Through-holes are provided to secure the condenser to a
curb, rack or wooden timber.
n
Warning
The ice machine head section contains refrigerant charge.
The ice machine head section contains refrigeration
valves that must remain closed until proper installation of
the line sets is completed.
n
Warning
Electrical power to the ice machine head section,
condensing unit or condenser must be disconnected
before proceeding.
Step 2 Route the Refrigeration Tubing.
Route the refrigeration tubing between the ice machine head
section and the condenser or ICVD® condensing unit.
Maximum lineset exposed on rooftop is 25% of total line
set length.
A qualified person must perform all roof penetrations.
QuietQube Models Only
A suction line oil trap is required when rise is more than 6
meters (20 feet).
Only one trap is allowed in the lineset.
Shorten the lineset as required, do not coil lineset.
10 METER (30
FEET) MAX.
DISTANCE
30 METER (100 FEET)
MAX. LINESET LENGTH
QUIETQUBE MODELS ONLY: WITH
MORE THAN 6 METER (20 FEET) RISE,
S-TRAP KIT IS REQUIRED
Manitowoc S-Trap Kit
Model
S-Trap Kit
Number
Tubing Size
I0680C IB0686C IB690C
I0686C I0696C I0870C
I0876C IB890C I0976C
I1070C I1076C IB1090C
IB1096C I1176C
K00172
16 mm
(5/8 inch)
I1470C I1476C I1870C
I1876C I2170C I2176C
K00166
19 mm
(3/4 inch)