Service manual
36
Refrigeration System
Safety Limit #2
Harvest time exceeds 3.5 minutes for 3 consecutive harvest cycles.
Possible Cause Check/Correct
Improper installation • See “Installation/Visual Inspection Checklist” on page 7-10
Water system • Water area (evaporator) dirty
• Dirty/defective water dump valve
• Vent tube not installed on water outlet drain
• Water freezing behind evaporator
• Plastic extrusions and gaskets not securely mounted to the evaporator
• Low water pressure (20 psi min.)
• Loss of water from sump area
• Clogged water distribution tube
• Dirty/defective water fill valve
• Defective water pump
Electrical system • Ice thickness probe out of adjustment
• Ice thickness probe dirty
• Bin switch defective
• Premature harvest
Refrigeration system • Non-Manitowoc components
• Water regulating valve dirty/defective
• Improper refrigerant charge
• Defective hot gas valve
• TXV flooding (check bulb mounting)
SAFETY LIMIT NOTES
• Because there are many possible external problems, do not limit your diagnosis to only the items listed in
this chart.
• A continuous run of 100 harvests automatically erases the safety limit code.
• The control board will store and indicate only one safety limit – the last one exceeded.
• If the toggle switch is moved to the OFF position and then back to the ICE position prior to reaching the
100-harvest point, the last safety limit exceeded will be indicated.
• If the harvest light did not flash prior to the ice machine restarting, then the ice machine did not stop
because it exceeded a safety limit.