Service manual

36
Refrigeration System
Safety Limit #2
Harvest time exceeds 3.5 minutes for 3 consecutive harvest cycles.
Possible Cause Check/Correct
Improper installation See “Installation/Visual Inspection Checklist” on page 7-10
Water system Water area (evaporator) dirty
Dirty/defective water dump valve
Vent tube not installed on water outlet drain
Water freezing behind evaporator
Plastic extrusions and gaskets not securely mounted to the evaporator
Low water pressure (20 psi min.)
Loss of water from sump area
Clogged water distribution tube
Dirty/defective water fill valve
Defective water pump
Electrical system Ice thickness probe out of adjustment
Ice thickness probe dirty
Bin switch defective
Premature harvest
Refrigeration system Non-Manitowoc components
Water regulating valve dirty/defective
Improper refrigerant charge
Defective hot gas valve
TXV flooding (check bulb mounting)
SAFETY LIMIT NOTES
Because there are many possible external problems, do not limit your diagnosis to only the items listed in
this chart.
A continuous run of 100 harvests automatically erases the safety limit code.
The control board will store and indicate only one safety limit – the last one exceeded.
If the toggle switch is moved to the OFF position and then back to the ICE position prior to reaching the
100-harvest point, the last safety limit exceeded will be indicated.
If the harvest light did not flash prior to the ice machine restarting, then the ice machine did not stop
because it exceeded a safety limit.