Refrigeration System Section 7
7-60 Part No. 80-1100-3
HFC REFRIGERANT QUESTIONS AND ANSWERS
Manitowoc uses R-404A and R-134A HFC refrigerants 
with ozone depletion potential (ODP) factors of zero 
(0.0). R-404A is used in ice machines and reach-in 
freezers and R-134A is used in reach-in refrigerators.
1. What compressor oil does Manitowoc require for 
use with HFC refrigerants?
Manitowoc products use Polyol Ester (POE) type 
compressor oil. It is the lubricant of choice among 
compressor manufacturers.
2. What are some of the characteristics of POE oils?
They are hygroscopic, which means they have the 
ability to absorb moisture. POE oils are 100 times 
more hygroscopic than mineral oils. Once moisture 
is absorbed into the oil, it is difficult to remove, even 
with heat and vacuum. POE oils are also excellent 
solvents, and tend to “solvent clean” everything 
inside the system, depositing material where it is not 
wanted.
3. What do these POE oil characteristics mean to me?
You must be more exacting in your procedures. Take 
utmost care to prevent moisture from entering the 
refrigeration system. Refrigeration systems and 
compressors should not be left open to the 
atmosphere for more than 15 minutes. Keep oil 
containers and compressors capped at all times to 
minimize moisture entry. Before removing the 
system charge to replace a faulty component, be 
sure you have all of the needed components at the 
site. Remove new system component plugs and 
caps just prior to brazing. Be prepared to connect a 
vacuum pump immediately after brazing.
4. Are there any special procedures required if a POE 
system is diagnosed with a refrigerant leak?
For systems found with
 positive refrigerant system 
pressure, no special procedures are required.
For systems found without
 any positive refrigerant 
pressure, assume that moisture has entered the 
POE oil. After the leak is found and repaired, the 
compressor oil must be changed. The compressor 
must be removed and at least 95% of the oil drained 
from the suction port of the compressor. Use a 
“measuring cup” to replace the old oil with exactly 
the same amount of new POE oil, such as Mobil 
EAL22A.
Remember, care must be taken to prevent moisture 
from getting into the refrigeration system during 
refrigeration repairs.
5. How do I leak-check a system containing HFC 
refrigerant?
Use equipment designed for HFC detection. Do not 
use equipment designed for CFC detection. Consult 
leak detection equipment manufacturers for their 
recommendations. Also, standard soap bubbles will 
work with HFC refrigerants.
6. Does Manitowoc use a special liquid line filter-drier 
with HFC refrigerants?
Yes. Manitowoc uses an ALCO “UK” series filter-
drier for increased filtration and moisture removal. 
During a repair, Manitowoc recommends installing 
the drier just before hooking up a vacuum pump.