Service manual
Section 2 Installation Instructions
Part No. 80-1100-3 2-11
Water Supply and Drain Requirements
WATER SUPPLY
Local water conditions may require treatment of the 
water to inhibit scale formation, filter sediment, and 
remove chlorine odor and taste.
WATER INLET LINES
Follow these guidelines to install water inlet lines:
• Do not connect the ice machine to a hot water 
supply. Be sure all hot water restrictors installed for 
other equipment are working. (Check valves on sink 
faucets, dishwashers, etc.)
• If water pressure exceeds the maximum 
recommended pressure, obtain a water pressure 
regulator from your Manitowoc distributor.
• Install a water shut-off valve for both the ice making 
and condenser water lines.
• Insulate water inlet lines to prevent condensation.
DRAIN CONNECTIONS
Follow these guidelines when installing drain lines to 
prevent drain water from flowing back into the ice 
machine and storage bin:
• Drain lines must have a 1.5 inch drop per 5 feet of 
run (2.5 cm per meter), and must not create traps.
• The floor drain must be large enough to 
accommodate drainage from all drains.
• Run separate bin and ice machine drain lines. 
Insulate them to prevent condensation.
• Vent the bin and ice machine drain to the 
atmosphere. Do not vent the condenser drain on 
water-cooled models.
Cooling Tower Applications
(Water-Cooled Models)
A water cooling tower installation does not require 
modification of the ice machine. The water regulator 
valve for the condenser continues to control the 
refrigeration discharge pressure.
It is necessary to know the amount of heat rejection, and 
the pressure drop through the condenser and water 
valves (inlet and outlet) when using a cooling tower on 
an ice machine.
• Water entering the condenser must not exceed 90°F 
(32.2°C).
• Water flow through the condenser must not exceed 5 
gallons (19 liters) per minute.
• Allow for a pressure drop of 7 psi (48 kPA) between 
the condenser water inlet and the outlet of the ice 
machine.
• Water exiting the condenser must not exceed 110°F 
(43.3°C).
Important
If you are installing a Manitowoc water filter system,
refer to the Installation Instructions supplied with the
filter system for ice making water inlet connections.