RNF0620/RFF0620/RNF1100/RFF1300/RFF2500
OPERATION
When the toggle switch is placed in the ON position the
following controls must be in the closed position before
the ice machine will start:
A. Bin Thermostat
B. High Pressure Cut-out Switch
C. Ice Chute Safety Switch
D. Low Pressure Switch
E. Low Water Level Switch
Placing the toggle switch in the ON position starts the
gear motor. After the rotation speed sensor verifies 10
minutes of correct rotation, the time delay ends and the
compressor starts. The ice machine will continue to make
ice until ice contacts the bin thermostat. The ice machine
remains off until ice no longer contacts the bin thermostat.