Operator`s manual
WRO 300
P/N 3027435 Rev. C
Regular Maintenance
17
3 Regular Maintenance
3.1 Chemical Disinfection
The required chemical disinfection frequency to achieve the desired
microbiological requirements for the product water depends on several
factors, such as:
• The quality of the feed water.
• Local regulations regarding the microbiological quality of dialysis
water, etc.
• Local preferences, for example regarding the use of chemicals.
No general rules can be given that cover all situations. The disinfection
schedule should instead be based upon microbiological testing per-
formed by the clinic. A maximum period between disinfections should
then be established to ensure acceptable bacteriological quality of the
product water according to the clinic standards.
As a guideline, MCP recommends a minimum frequency of weekly
chemical disinfection to ensure consistent microbiological quality of the
product water.
The use of an ultrafilter on the dialysis machine will remove possible
contaminants originating from the product water and may therefore be
used as a method to extend the time between chemical disinfection of
the WRO 300.
If the WRO 300 will not be used for an extended period of time, weekly
chemical disinfection will help maintain the microbiological quality of
the product water.
For certain peracetic acid disinfectants, the manufacturer recommends
that the WRO 300 be cleaned with an acid cleaning agent in accor-
dance with the cleaning instructions prior to chemical disinfection.
Refer to the section, Cleaning on page 23.
3.1.1 Approved Chemical Disinfectants
•MINNCARE
®
Cold Sterilant
Required amount: 50 ml of concentrated disinfectant
NOTE
The procedure below assume factory settings of the protocol.
CAUTION
Disinfectants may be toxic. Refer to the manufacturer Instruc-
tions.










